Skip to Content

Dry cooler BE-t-2x280GC1-B01C C

Dry cooler BE-t-2x280GC1-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x280GC1-B01C C

Heat rejection i
306.76 kW
Air flow
76,136 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 76,136 m³/h
External surface 799.6 m²
Inner volume 112.3 dm³
Fin materialAluminium
Net weight 1,183 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.1 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-t-2x280GC1-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
306.761 kW Fluid flow 53.20 m³/h Pressure drop 53.1 kPa
Heat rejection · Low speed (Y)
232.889 kW Fluid flow 40.39 m³/h Pressure drop 32.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 182.47 not rated not rated not rated not rated not rated
40 306.76 182.90 not rated not rated not rated not rated
45 426.99 306.07 183.22 not rated not rated not rated
50 545.84 425.35 305.49 183.58 not rated not rated
55 664.04 543.32 423.97 305.10 184.05 not rated
60 781.88 660.66 541.18 422.92 305.04 184.71

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 140.18 not rated not rated not rated not rated not rated
40 232.89 140.40 not rated not rated not rated not rated
45 322.15 232.13 140.59 not rated not rated not rated
50 410.29 320.61 231.52 140.82 not rated not rated
55 497.90 408.01 319.34 231.13 141.16 not rated
60 585.23 494.92 406.14 318.45 231.04 141.66

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 306.761 53.20 53.1
Low speed (Y) 232.889 40.39 32.5

Dimensions

Dimension drawing of BE-t-2x280GC1-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 2650 mm
F 2230 mm
G 3250 mm
E1 1150 mm
H 2900 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3250 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.