Skip to Content

Dry cooler BE-2X280AC1-B01T C

Dry cooler BE-2X280AC1-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2X280AC1-B01T C

Heat rejection i
306.50 kW
Air flow
82,651 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 2 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
  • K
    Delivery version (optional): T — T: truck delivery version

Data

Coil
Air flow 82,651 m³/h
External surface 1,340.2 m²
Inner volume 175.8 dm³
Fin materialAluminium
Net weight 1,465 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2X280AC1-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
306.495 kW Fluid flow 53.16 m³/h Pressure drop 62.0 kPa
Heat rejection · Low speed (Y)
238.349 kW Fluid flow 41.34 m³/h Pressure drop 39.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 181.64 not rated not rated not rated not rated not rated
40 306.50 181.78 not rated not rated not rated not rated
45 427.99 305.57 181.90 not rated not rated not rated
50 548.34 426.10 304.77 182.04 not rated not rated
55 668.17 545.54 424.48 304.18 182.29 not rated
60 787.71 664.47 543.14 423.24 303.90 182.69

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 142.73 not rated not rated not rated not rated not rated
40 238.35 142.79 not rated not rated not rated not rated
45 331.11 237.53 142.81 not rated not rated not rated
50 422.91 329.51 236.83 142.90 not rated not rated
55 514.26 420.58 328.17 236.33 143.09 not rated
60 605.36 511.22 418.61 327.15 236.09 143.42

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 306.495 53.16 62.0
Low speed (Y) 238.349 41.34 39.6

Dimensions

Dimension drawing of BE-2X280AC1-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 2850 mm
F 2330 mm
G 3450 mm
E1 1250 mm
H 3100 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3450 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.