BE-t-2x280HC1-B01C C
379.17 kW
Defrost: None
Product code: BE-2x280CC1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 89,178 m³/h |
|---|---|
| External surface | 2,681.2 m² |
| Inner volume | 327.4 dm³ |
| Fin material | Aluminium |
| Net weight | 2,066 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-2x280CC1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 231.27 | not rated | not rated | not rated | not rated | not rated |
| 40 | 378.39 | 230.46 | not rated | not rated | not rated | not rated |
| 45 | 521.16 | 375.91 | 229.69 | not rated | not rated | not rated |
| 50 | 662.49 | 517.18 | 373.72 | 229.07 | not rated | not rated |
| 55 | 803.17 | 657.07 | 513.67 | 371.90 | 228.66 | not rated |
| 60 | 943.49 | 796.33 | 652.30 | 510.76 | 370.56 | 228.55 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 179.67 | not rated | not rated | not rated | not rated | not rated |
| 40 | 291.11 | 178.92 | not rated | not rated | not rated | not rated |
| 45 | 399.04 | 289.00 | 178.23 | not rated | not rated | not rated |
| 50 | 505.84 | 395.73 | 287.14 | 177.66 | not rated | not rated |
| 55 | 612.14 | 501.39 | 392.83 | 285.61 | 177.29 | not rated |
| 60 | 718.15 | 606.55 | 497.48 | 390.42 | 284.48 | 177.16 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 378.385 | 65.62 | 54.0 |
| Low speed (Y) | 291.108 | 50.49 | 33.9 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 5250 mm |
| F | 2330 mm |
| G | 5850 mm |
| E1 | 2450 mm |
| H | 5500 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.