BE-2x380BB5-B01T C
335.94 kW
Defrost: None
Product code: BE-2x280DC1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 87,667 m³/h |
|---|---|
| External surface | 1,550.2 m² |
| Inner volume | 189.9 dm³ |
| Fin material | Aluminium |
| Net weight | 1,643 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-2x280DC1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 202.54 | not rated | not rated | not rated | not rated | not rated |
| 40 | 336.32 | 202.17 | not rated | not rated | not rated | not rated |
| 45 | 466.57 | 334.68 | 201.79 | not rated | not rated | not rated |
| 50 | 595.69 | 463.81 | 333.24 | 201.52 | not rated | not rated |
| 55 | 724.25 | 591.81 | 461.37 | 332.06 | 201.34 | not rated |
| 60 | 852.52 | 719.29 | 588.41 | 459.37 | 331.23 | 201.41 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 158.51 | not rated | not rated | not rated | not rated | not rated |
| 40 | 261.12 | 158.14 | not rated | not rated | not rated | not rated |
| 45 | 360.78 | 259.70 | 157.79 | not rated | not rated | not rated |
| 50 | 459.48 | 358.43 | 258.45 | 157.53 | not rated | not rated |
| 55 | 557.75 | 456.24 | 356.37 | 257.44 | 157.39 | not rated |
| 60 | 655.78 | 553.63 | 453.40 | 354.70 | 256.75 | 157.43 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 336.315 | 58.33 | 85.4 |
| Low speed (Y) | 261.117 | 45.29 | 54.5 |
| A | 2778 mm |
|---|---|
| B | 2400 mm |
| C | 4050 mm |
| F | 2330 mm |
| G | 4650 mm |
| E1 | 1850 mm |
| H | 4300 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 4650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2778 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.