BE-2x280DC1-B01T C
336.32 kW
Defrost: None
Product code: BE-2x380BB5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 127,983 m³/h |
|---|---|
| External surface | 902.8 m² |
| Inner volume | 143.4 dm³ |
| Fin material | Aluminium |
| Net weight | 1,701 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-2x380BB5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 193.23 | not rated | not rated | not rated | not rated | not rated |
| 40 | 335.94 | 193.96 | not rated | not rated | not rated | not rated |
| 45 | 475.64 | 335.79 | 194.58 | not rated | not rated | not rated |
| 50 | 614.39 | 474.73 | 335.66 | 195.13 | not rated | not rated |
| 55 | 752.70 | 612.76 | 473.95 | 335.63 | 195.69 | not rated |
| 60 | 890.78 | 750.37 | 611.36 | 473.39 | 335.74 | 196.30 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 156.33 | not rated | not rated | not rated | not rated | not rated |
| 40 | 270.24 | 156.90 | not rated | not rated | not rated | not rated |
| 45 | 381.44 | 270.03 | 157.37 | not rated | not rated | not rated |
| 50 | 491.81 | 380.58 | 269.86 | 157.83 | not rated | not rated |
| 55 | 601.77 | 490.32 | 379.85 | 269.77 | 158.27 | not rated |
| 60 | 711.52 | 599.69 | 489.06 | 379.31 | 269.84 | 158.77 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 335.937 | 58.30 | 61.8 |
| Low speed (Y) | 270.239 | 46.90 | 41.9 |
| A | 2778 mm |
|---|---|
| B | 2400 mm |
| C | 3750 mm |
| F | 2330 mm |
| G | 4350 mm |
| E1 | 1150 mm |
| E2 | 1100 mm |
| H | 4000 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 4350 mm |
|---|---|
| Width | 2400 mm |
| Height | 2778 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.