Skip to Content

Dry cooler BE-2x291DB1-C04C C

Dry cooler BE-2x291DB1-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x291DB1-C04C C

Heat rejection i
334.70 kW
Air flow
114,811 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 114,811 m³/h
External surface 951.2 m²
Inner volume 125.9 dm³
Fin materialAluminium
Net weight 1,383 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 64.0 dB(A)
Sound power 96.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2x291DB1-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
334.697 kW Fluid flow 58.09 m³/h Pressure drop 89.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
270.382 kW Fluid flow 46.93 m³/h Pressure drop 61.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 194.39 not rated not rated not rated not rated not rated
40 334.70 194.85 not rated not rated not rated not rated
45 471.94 334.24 195.24 not rated not rated not rated
50 608.20 470.65 333.83 195.62 not rated not rated
55 744.00 606.12 469.53 333.56 196.01 not rated
60 879.55 741.14 604.31 468.67 333.50 196.51

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 158.07 not rated not rated not rated not rated not rated
40 270.38 158.39 not rated not rated not rated not rated
45 379.99 269.88 158.65 not rated not rated not rated
50 488.74 378.76 269.44 158.90 not rated not rated
55 597.08 486.82 377.70 269.13 159.21 not rated
60 705.21 594.49 485.16 376.90 269.02 159.60

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 334.697 58.09 89.2
Low speed (Y) 270.382 46.93 61.0

Dimensions

Dimension drawing of BE-2x291DB1-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 4050 mm
F 2230 mm
G 4650 mm
E1 1850 mm
H 4300 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 4050 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.