Dry cooler BE-2x280DC5-B01C C

Dry cooler BE-2x280DC5-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x280DC5-B01C C

Heat rejection i
298.25 kW
Air flow
86,803 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 86,803 m³/h
External surface 1,108.4 m²
Inner volume 161.0 dm³
Fin materialAluminium
Net weight 1,430 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2x280DC5-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
298.245 kW Fluid flow 51.76 m³/h Pressure drop 90.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
234.507 kW Fluid flow 40.70 m³/h Pressure drop 58.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 177.46 not rated not rated not rated not rated not rated
40 298.25 177.35 not rated not rated not rated not rated
45 416.15 297.18 177.24 not rated not rated not rated
50 533.10 414.23 296.26 177.17 not rated not rated
55 649.60 530.31 412.54 295.51 177.19 not rated
60 765.89 646.02 527.90 411.14 295.03 177.35

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 140.57 not rated not rated not rated not rated not rated
40 234.51 140.44 not rated not rated not rated not rated
45 325.98 233.53 140.29 not rated not rated not rated
50 416.68 324.30 232.70 140.20 not rated not rated
55 507.02 414.31 322.84 232.04 140.19 not rated
60 597.16 503.96 412.24 321.66 231.60 140.32

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 298.245 51.76 90.2
Low speed (Y) 234.507 40.70 58.9

Dimensions

Dimension drawing of BE-2x280DC5-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 4050 mm
F 2230 mm
G 4650 mm
E1 1850 mm
H 4300 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 4650 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.