Dry cooler BE-2x291BC5-C04C C

Dry cooler BE-2x291BC5-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x291BC5-C04C C

Heat rejection i
296.33 kW
Air flow
104,989 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 104,989 m³/h
External surface 716.2 m²
Inner volume 115.8 dm³
Fin materialAluminium
Net weight 1,223 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 64.0 dB(A)
Sound power 96.4 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2x291BC5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
296.328 kW Fluid flow 51.43 m³/h Pressure drop 66.7 kPa
Heat rejection · Low speed (Y)
235.820 kW Fluid flow 40.92 m³/h Pressure drop 44.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 170.87 not rated not rated not rated not rated not rated
40 296.33 171.61 not rated not rated not rated not rated
45 419.03 296.36 172.28 not rated not rated not rated
50 540.83 418.44 296.42 172.85 not rated not rated
55 662.26 539.67 417.99 296.57 173.48 not rated
60 783.44 660.53 538.75 417.75 296.89 174.19

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 136.92 not rated not rated not rated not rated not rated
40 235.82 137.55 not rated not rated not rated not rated
45 332.27 235.85 138.09 not rated not rated not rated
50 427.91 331.79 235.91 138.62 not rated not rated
55 523.21 426.98 331.45 236.07 139.17 not rated
60 618.30 521.82 426.26 331.31 236.39 139.80

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 296.328 51.43 66.7
Low speed (Y) 235.820 40.92 44.5

Dimensions

Dimension drawing of BE-2x291BC5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 2850 mm
F 2230 mm
G 3450 mm
E1 1230 mm
H 3100 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 2850 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.