BE-t-2x480GB5-B01C C
506.36 kW
Defrost: None
Product code: BE-2x380DC1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 131,500 m³/h |
|---|---|
| External surface | 2,325.0 m² |
| Inner volume | 277.9 dm³ |
| Fin material | Aluminium |
| Net weight | 2,292 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-2x380DC1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 306.04 | not rated | not rated | not rated | not rated | not rated |
| 40 | 506.38 | 305.31 | not rated | not rated | not rated | not rated |
| 45 | 701.61 | 503.79 | 304.62 | not rated | not rated | not rated |
| 50 | 895.18 | 697.36 | 501.53 | 304.09 | not rated | not rated |
| 55 | 1087.96 | 889.28 | 693.62 | 499.67 | 303.69 | not rated |
| 60 | 1280.31 | 1080.44 | 884.10 | 690.54 | 498.36 | 303.72 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 239.47 | not rated | not rated | not rated | not rated | not rated |
| 40 | 393.05 | 238.77 | not rated | not rated | not rated | not rated |
| 45 | 542.40 | 390.83 | 238.14 | not rated | not rated | not rated |
| 50 | 690.37 | 538.80 | 388.87 | 237.63 | not rated | not rated |
| 55 | 837.71 | 685.43 | 535.65 | 387.29 | 237.34 | not rated |
| 60 | 984.70 | 831.46 | 681.13 | 533.07 | 386.18 | 237.34 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 506.378 | 87.82 | 114.8 |
| Low speed (Y) | 393.051 | 68.17 | 73.2 |
| A | 2778 mm |
|---|---|
| B | 2400 mm |
| C | 5850 mm |
| F | 2330 mm |
| G | 6450 mm |
| E1 | 1850 mm |
| E2 | 1800 mm |
| H | 6100 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 6450 mm |
|---|---|
| Width | 2400 mm |
| Height | 2778 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.