Skip to Content

Dry cooler BE-2x391DC1-B04T C

Dry cooler BE-2x391DC1-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x391DC1-B04T C

Heat rejection i
617.54 kW
Air flow
172,856 m³/h
Fans
6 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 172,856 m³/h
External surface 2,325.4 m²
Inner volume 317.4 dm³
Fin materialAluminium
Net weight 2,328 kg
Fans
Quantity 6
Diameter 910 mm
Speed 840 rpm
Power 16,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 65.0 dB(A)
Sound power 98.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x391DC1-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
617.536 kW Fluid flow 107.17 m³/h Pressure drop 52.8 kPa
Heat rejection · Low speed (Y)
488.478 kW Fluid flow 84.72 m³/h Pressure drop 34.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 364.86 not rated not rated not rated not rated not rated
40 617.54 365.15 not rated not rated not rated not rated
45 863.29 615.59 365.37 not rated not rated not rated
50 1106.90 859.38 613.88 365.60 not rated not rated
55 1349.51 1101.11 855.96 612.45 366.01 not rated
60 1591.52 1341.85 1096.04 853.21 611.67 366.67

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 290.85 not rated not rated not rated not rated not rated
40 488.48 290.99 not rated not rated not rated not rated
45 680.24 486.66 291.07 not rated not rated not rated
50 870.12 676.79 485.07 291.16 not rated not rated
55 1059.11 865.07 673.76 483.84 291.42 not rated
60 1247.60 1052.51 860.68 671.35 483.08 291.87

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 617.536 107.17 52.8
Low speed (Y) 488.478 84.72 34.7

Dimensions

Dimension drawing of BE-2x391DC1-B04T C
Dimension drawing
Dimensions as drawn
A 2910 mm
B 2400 mm
C 5850 mm
F 2330 mm
G 6450 mm
E1 1850 mm
E2 1800 mm
H 6100 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6450 mm
Width 2400 mm
Height 2910 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.