Skip to Content

Dry cooler BE-2x580BB1-B01T C

Dry cooler BE-2x580BB1-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x580BB1-B01T C

Heat rejection i
619.41 kW
Air flow
211,405 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 211,405 m³/h
External surface 1,776.3 m²
Inner volume 264.8 dm³
Fin materialAluminium
Net weight 2,660 kg
Fans
Quantity 10
Diameter 800 mm
Speed 900 rpm
Power 18,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 90.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x580BB1-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
619.409 kW Fluid flow 107.50 m³/h Pressure drop 85.6 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
493.514 kW Fluid flow 85.65 m³/h Pressure drop 57.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 360.10 not rated not rated not rated not rated not rated
40 619.41 360.98 not rated not rated not rated not rated
45 873.05 618.65 361.76 not rated not rated not rated
50 1124.90 870.82 618.01 362.48 not rated not rated
55 1375.87 1121.24 868.91 617.61 363.25 not rated
60 1626.39 1370.83 1118.12 867.52 617.56 364.17

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 288.91 not rated not rated not rated not rated not rated
40 493.51 289.51 not rated not rated not rated not rated
45 693.17 492.65 290.01 not rated not rated not rated
50 891.24 691.01 491.92 290.53 not rated not rated
55 1088.55 887.85 689.21 491.45 291.12 not rated
60 1285.49 1083.99 884.99 687.83 491.31 291.88

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 619.409 107.50 85.6
Low speed (Y) 493.514 85.65 57.2

Dimensions

Dimension drawing of BE-2x580BB1-B01T C
Dimension drawing
Dimensions as drawn
A 2778 mm
B 2400 mm
C 5950 mm
F 2330 mm
G 6550 mm
E1 1150 mm
E2 3300 mm
H 6200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6550 mm
Width 2400 mm
Height 2778 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.