Skip to Content

Dry cooler BE-691ED5-B04 C

Dry cooler BE-691ED5-B04 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-691ED5-B04 C

Heat rejection i
618.36 kW
Air flow
157,452 m³/h
Fans
6 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 157,452 m³/h
External surface 2,271.1 m²
Inner volume 516.0 dm³
Fin materialAluminium
Net weight 2,001 kg
Fans
Quantity 6
Diameter 910 mm
Speed 840 rpm
Power 16,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 98.4 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-691ED5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
618.356 kW Fluid flow 107.23 m³/h Pressure drop 107.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
474.143 kW Fluid flow 82.23 m³/h Pressure drop 67.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 374.60 not rated not rated not rated not rated not rated
40 618.36 374.03 not rated not rated not rated not rated
45 855.99 615.92 373.55 not rated not rated not rated
50 1091.53 851.77 613.85 373.23 not rated not rated
55 1326.12 1085.62 848.23 612.33 373.28 not rated
60 1560.17 1318.53 1080.63 845.54 611.52 373.80

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 290.13 not rated not rated not rated not rated not rated
40 474.14 289.65 not rated not rated not rated not rated
45 653.14 472.21 289.27 not rated not rated not rated
50 830.47 649.88 470.63 289.13 not rated not rated
55 1007.04 825.94 647.20 469.55 289.25 not rated
60 1183.20 1001.25 822.20 645.27 469.08 289.78

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 618.356 107.23 107.9
Low speed (Y) 474.143 82.23 67.4

Dimensions

Dimension drawing of BE-691ED5-B04 C
Dimension drawing
Dimensions as drawn
A 1958 mm
B 1300 mm
C 7660 mm
F 1150 mm
G 8260 mm
E1 1230 mm
E2 1200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 8260 mm
Width 1300 mm
Height 1958 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.