BE-2x580BB1-B01T C
619.41 kW
Defrost: None
Product code: BE-t-2x491GB5-C04C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 212,178 m³/h |
|---|---|
| External surface | 1,074.3 m² |
| Inner volume | 201.1 dm³ |
| Fin material | Aluminium |
| Net weight | 2,033 kg |
| Quantity | 8 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 22,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 67.0 dB(A) |
|---|---|
| Sound power | 99.2 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-t-2x491GB5-C04C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 357.50 | not rated | not rated | not rated | not rated | not rated |
| 40 | 619.81 | 358.90 | not rated | not rated | not rated | not rated |
| 45 | 876.40 | 619.66 | 360.11 | not rated | not rated | not rated |
| 50 | 1131.16 | 874.86 | 619.59 | 361.27 | not rated | not rated |
| 55 | 1385.03 | 1128.29 | 873.62 | 619.73 | 362.51 | not rated |
| 60 | 1638.43 | 1380.87 | 1125.93 | 872.85 | 620.27 | 363.88 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 289.13 | not rated | not rated | not rated | not rated | not rated |
| 40 | 497.03 | 290.23 | not rated | not rated | not rated | not rated |
| 45 | 699.83 | 496.83 | 291.21 | not rated | not rated | not rated |
| 50 | 900.97 | 698.51 | 496.73 | 292.18 | not rated | not rated |
| 55 | 1101.34 | 898.57 | 697.47 | 496.90 | 293.24 | not rated |
| 60 | 1301.28 | 1097.89 | 896.63 | 696.89 | 497.40 | 294.46 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 619.812 | 107.57 | 87.7 |
| Low speed (Y) | 497.033 | 86.26 | 59.3 |
| A | 2511 mm |
|---|---|
| B | 2300 mm |
| C | 5250 mm |
| F | 2230 mm |
| G | 5850 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| H | 5500 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5250 mm |
|---|---|
| Width | 2300 mm |
| Height | 2511 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.