BE-2x580AD1-B01C C
775.04 kW
Defrost: None
Product code: BE-2x591AC5-C04C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 259,570 m³/h |
|---|---|
| External surface | 2,336.0 m² |
| Inner volume | 359.1 dm³ |
| Fin material | Aluminium |
| Net weight | 2,783 kg |
| Quantity | 10 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 28,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 100.5 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2x591AC5-C04C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 445.78 | not rated | not rated | not rated | not rated | not rated |
| 40 | 775.35 | 447.85 | not rated | not rated | not rated | not rated |
| 45 | 1097.42 | 775.41 | 449.67 | not rated | not rated | not rated |
| 50 | 1417.06 | 1095.69 | 775.56 | 451.42 | not rated | not rated |
| 55 | 1735.54 | 1413.65 | 1094.40 | 776.01 | 453.17 | not rated |
| 60 | 2053.43 | 1730.49 | 1410.89 | 1093.64 | 776.87 | 455.12 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 358.60 | not rated | not rated | not rated | not rated | not rated |
| 40 | 618.06 | 360.25 | not rated | not rated | not rated | not rated |
| 45 | 870.81 | 618.00 | 361.71 | not rated | not rated | not rated |
| 50 | 1121.32 | 869.29 | 618.11 | 363.16 | not rated | not rated |
| 55 | 1370.83 | 1118.46 | 868.20 | 618.47 | 364.66 | not rated |
| 60 | 1619.67 | 1366.56 | 1116.16 | 867.69 | 619.33 | 366.38 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 775.354 | 134.57 | 51.3 |
| Low speed (Y) | 618.061 | 107.26 | 34.2 |
| A | 2511 mm |
|---|---|
| B | 2300 mm |
| C | 6450 mm |
| F | 2230 mm |
| G | 7050 mm |
| E1 | 1250 mm |
| E2 | 3600 mm |
| H | 6700 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 6450 mm |
|---|---|
| Width | 2300 mm |
| Height | 2511 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.