Skip to Content

Dry cooler BE-2x591AC5-C04C C

Dry cooler BE-2x591AC5-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x591AC5-C04C C

Heat rejection i
775.35 kW
Air flow
259,570 m³/h
Fans
10 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 5 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: C — generation C
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
  • K
    Delivery version (optional): C — C: container delivery version

Data

Coil
Air flow 259,570 m³/h
External surface 2,336.0 m²
Inner volume 359.1 dm³
Fin materialAluminium
Net weight 2,783 kg
Fans
Quantity 10
Diameter 910 mm
Speed 840 rpm
Power 28,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 68.0 dB(A)
Sound power 100.5 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x591AC5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
775.354 kW Fluid flow 134.57 m³/h Pressure drop 51.3 kPa
Heat rejection · Low speed (Y)
618.061 kW Fluid flow 107.26 m³/h Pressure drop 34.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 445.78 not rated not rated not rated not rated not rated
40 775.35 447.85 not rated not rated not rated not rated
45 1097.42 775.41 449.67 not rated not rated not rated
50 1417.06 1095.69 775.56 451.42 not rated not rated
55 1735.54 1413.65 1094.40 776.01 453.17 not rated
60 2053.43 1730.49 1410.89 1093.64 776.87 455.12

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 358.60 not rated not rated not rated not rated not rated
40 618.06 360.25 not rated not rated not rated not rated
45 870.81 618.00 361.71 not rated not rated not rated
50 1121.32 869.29 618.11 363.16 not rated not rated
55 1370.83 1118.46 868.20 618.47 364.66 not rated
60 1619.67 1366.56 1116.16 867.69 619.33 366.38

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 775.354 134.57 51.3
Low speed (Y) 618.061 107.26 34.2

Dimensions

Dimension drawing of BE-2x591AC5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 6450 mm
F 2230 mm
G 7050 mm
E1 1250 mm
E2 3600 mm
H 6700 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6450 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.