BE-980ED1-B01 C
776.09 kW
Defrost: None
Product code: BE-t-2x580GC1-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 190,339 m³/h |
|---|---|
| External surface | 1,999.1 m² |
| Inner volume | 273.2 dm³ |
| Fin material | Aluminium |
| Net weight | 2,520 kg |
| Quantity | 10 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 18,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.1 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-t-2x580GC1-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 466.64 | not rated | not rated | not rated | not rated | not rated |
| 40 | 775.88 | 466.84 | not rated | not rated | not rated | not rated |
| 45 | 1075.83 | 773.61 | 467.11 | not rated | not rated | not rated |
| 50 | 1372.61 | 1071.28 | 771.69 | 467.49 | not rated | not rated |
| 55 | 1667.92 | 1365.90 | 1067.44 | 770.32 | 468.24 | not rated |
| 60 | 1962.41 | 1659.11 | 1360.23 | 1064.47 | 769.84 | 469.50 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 358.05 | not rated | not rated | not rated | not rated | not rated |
| 40 | 588.28 | 357.96 | not rated | not rated | not rated | not rated |
| 45 | 810.80 | 585.98 | 357.93 | not rated | not rated | not rated |
| 50 | 1030.79 | 806.61 | 584.11 | 358.08 | not rated | not rated |
| 55 | 1249.61 | 1024.82 | 803.16 | 582.84 | 358.59 | not rated |
| 60 | 1467.78 | 1241.90 | 1019.89 | 800.69 | 582.37 | 359.56 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 775.878 | 134.56 | 87.8 |
| Low speed (Y) | 588.276 | 102.04 | 53.7 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 5950 mm |
| F | 2230 mm |
| G | 6550 mm |
| E1 | 1150 mm |
| E2 | 3300 mm |
| H | 6200 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 6550 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.