BE-980ED1-B01 C
776.09 kW
Defrost: None
Product code: BE-2x591EB1-C04C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 257,663 m³/h |
|---|---|
| External surface | 1,966.7 m² |
| Inner volume | 408.2 dm³ |
| Fin material | Aluminium |
| Net weight | 2,709 kg |
| Quantity | 10 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 28,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 100.6 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2x591EB1-C04C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 450.38 | not rated | not rated | not rated | not rated | not rated |
| 40 | 776.87 | 451.87 | not rated | not rated | not rated | not rated |
| 45 | 1096.35 | 776.56 | 453.25 | not rated | not rated | not rated |
| 50 | 1413.55 | 1094.38 | 776.41 | 454.57 | not rated | not rated |
| 55 | 1729.64 | 1409.98 | 1092.88 | 776.61 | 456.00 | not rated |
| 60 | 2045.18 | 1724.56 | 1407.11 | 1091.99 | 777.29 | 457.69 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 359.73 | not rated | not rated | not rated | not rated | not rated |
| 40 | 614.93 | 360.89 | not rated | not rated | not rated | not rated |
| 45 | 864.05 | 614.65 | 361.98 | not rated | not rated | not rated |
| 50 | 1111.12 | 862.40 | 614.51 | 363.07 | not rated | not rated |
| 55 | 1357.27 | 1108.23 | 861.22 | 614.71 | 364.31 | not rated |
| 60 | 1602.79 | 1353.06 | 1105.92 | 860.63 | 615.44 | 365.82 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 776.866 | 134.82 | 83.9 |
| Low speed (Y) | 614.931 | 106.72 | 55.3 |
| A | 2511 mm |
|---|---|
| B | 2300 mm |
| C | 6450 mm |
| F | 2230 mm |
| G | 7050 mm |
| E1 | 1250 mm |
| E2 | 3600 mm |
| H | 6700 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 6450 mm |
|---|---|
| Width | 2300 mm |
| Height | 2511 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.