BE-t-2x580GC1-B01C C
775.88 kW
Defrost: None
Product code: BE-980ED1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 180,236 m³/h |
|---|---|
| External surface | 4,021.0 m² |
| Inner volume | 744.7 dm³ |
| Fin material | Aluminium |
| Net weight | 3,017 kg |
| Quantity | 9 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 16,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.5 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-980ED1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 474.02 | not rated | not rated | not rated | not rated | not rated |
| 40 | 776.09 | 473.21 | not rated | not rated | not rated | not rated |
| 45 | 1068.73 | 772.30 | 472.53 | not rated | not rated | not rated |
| 50 | 1358.26 | 1062.28 | 769.09 | 472.12 | not rated | not rated |
| 55 | 1646.34 | 1349.28 | 1056.83 | 766.67 | 472.06 | not rated |
| 60 | 1933.64 | 1634.90 | 1341.68 | 1052.60 | 765.10 | 472.68 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 359.73 | not rated | not rated | not rated | not rated | not rated |
| 40 | 582.40 | 358.96 | not rated | not rated | not rated | not rated |
| 45 | 797.74 | 579.28 | 358.31 | not rated | not rated | not rated |
| 50 | 1010.69 | 792.59 | 576.66 | 357.91 | not rated | not rated |
| 55 | 1222.56 | 1003.63 | 788.28 | 574.72 | 357.91 | not rated |
| 60 | 1433.83 | 1213.64 | 997.70 | 785.00 | 573.64 | 358.46 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 776.094 | 134.61 | 41.5 |
| Low speed (Y) | 582.400 | 101.02 | 24.7 |
| A | 1808 mm |
|---|---|
| B | 1300 mm |
| C | 11260 mm |
| F | 1150 mm |
| G | 11860 mm |
| E1 | 1230 mm |
| E2 | 1200 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 11860 mm |
|---|---|
| Width | 1300 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.