BE-2x780EC5-B01C C
982.98 kW
Defrost: None
Product code: BE-2x680AD1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 241,373 m³/h |
|---|---|
| External surface | 5,027.2 m² |
| Inner volume | 653.1 dm³ |
| Fin material | Aluminium |
| Net weight | 4,204 kg |
| Quantity | 12 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 21,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x680AD1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 588.26 | not rated | not rated | not rated | not rated | not rated |
| 40 | 980.03 | 588.25 | not rated | not rated | not rated | not rated |
| 45 | 1359.78 | 976.42 | 588.25 | not rated | not rated | not rated |
| 50 | 1735.47 | 1352.92 | 973.23 | 588.42 | not rated | not rated |
| 55 | 2109.27 | 1725.51 | 1346.90 | 970.83 | 589.03 | not rated |
| 60 | 2482.02 | 2096.29 | 1716.80 | 1342.18 | 969.53 | 590.25 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 452.88 | not rated | not rated | not rated | not rated | not rated |
| 40 | 746.08 | 452.75 | not rated | not rated | not rated | not rated |
| 45 | 1029.26 | 742.91 | 452.63 | not rated | not rated | not rated |
| 50 | 1309.17 | 1023.52 | 740.27 | 452.72 | not rated | not rated |
| 55 | 1587.57 | 1301.01 | 1018.70 | 738.35 | 453.19 | not rated |
| 60 | 1865.12 | 1577.05 | 1294.15 | 1015.09 | 737.42 | 454.28 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 980.027 | 169.96 | 42.6 |
| Low speed (Y) | 746.080 | 129.41 | 26.2 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 7650 mm |
| F | 2330 mm |
| G | 8250 mm |
| E1 | 1250 mm |
| E2 | 1200 mm |
| E3 | 2400 mm |
| H | 7900 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 8250 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.