BE-t-2x580GC1-B01T C
837.16 kW
Defrost: None
Product code: BE-2x680EC5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 235,931 m³/h |
|---|---|
| External surface | 2,779.1 m² |
| Inner volume | 674.3 dm³ |
| Fin material | Aluminium |
| Net weight | 3,507 kg |
| Quantity | 12 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 21,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x680EC5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 496.57 | not rated | not rated | not rated | not rated | not rated |
| 40 | 837.04 | 497.07 | not rated | not rated | not rated | not rated |
| 45 | 1169.01 | 835.17 | 497.50 | not rated | not rated | not rated |
| 50 | 1498.33 | 1165.06 | 833.71 | 498.07 | not rated | not rated |
| 55 | 1826.38 | 1492.34 | 1161.76 | 832.65 | 498.97 | not rated |
| 60 | 2153.68 | 1818.35 | 1487.34 | 1159.47 | 832.49 | 500.26 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 388.19 | not rated | not rated | not rated | not rated | not rated |
| 40 | 647.92 | 388.35 | not rated | not rated | not rated | not rated |
| 45 | 900.72 | 646.12 | 388.56 | not rated | not rated | not rated |
| 50 | 1151.23 | 897.20 | 644.73 | 388.92 | not rated | not rated |
| 55 | 1400.64 | 1146.00 | 894.33 | 643.84 | 389.56 | not rated |
| 60 | 1649.44 | 1393.76 | 1141.73 | 892.33 | 643.65 | 390.50 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 837.039 | 145.28 | 61.5 |
| Low speed (Y) | 647.922 | 112.37 | 39.0 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 7650 mm |
| F | 2230 mm |
| G | 8250 mm |
| E1 | 1250 mm |
| E2 | 1200 mm |
| E3 | 2400 mm |
| H | 7900 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 8250 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.