BE-t-2x591GC1-B04T C
1059.01 kW
Defrost: None
Product code: BE-2x880AB1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 340,056 m³/h |
|---|---|
| External surface | 4,021.8 m² |
| Inner volume | 550.9 dm³ |
| Fin material | Aluminium |
| Net weight | 4,652 kg |
| Quantity | 16 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 28,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x880AB1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 601.64 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1058.49 | 605.17 | not rated | not rated | not rated | not rated |
| 45 | 1503.33 | 1058.16 | 608.10 | not rated | not rated | not rated |
| 50 | 1944.18 | 1499.71 | 1057.86 | 610.78 | not rated | not rated |
| 55 | 2383.29 | 1937.52 | 1496.51 | 1057.79 | 613.32 | not rated |
| 60 | 2821.38 | 2373.57 | 1931.63 | 1494.11 | 1058.29 | 616.03 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 484.07 | not rated | not rated | not rated | not rated | not rated |
| 40 | 844.39 | 486.79 | not rated | not rated | not rated | not rated |
| 45 | 1193.62 | 843.64 | 489.08 | not rated | not rated | not rated |
| 50 | 1539.19 | 1190.05 | 842.97 | 491.09 | not rated | not rated |
| 55 | 1883.20 | 1532.99 | 1186.87 | 842.66 | 493.10 | not rated |
| 60 | 2226.27 | 1874.45 | 1527.65 | 1184.61 | 842.91 | 495.30 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1058.485 | 183.70 | 26.8 |
| Low speed (Y) | 844.391 | 146.57 | 17.8 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 10050 mm |
| F | 2330 mm |
| G | 10650 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| H | 10300 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 10650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.