BE-2x880AB1-B01T C
1058.49 kW
Defrost: None
Product code: BE-t-2x591GC1-B04T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 263,109 m³/h |
|---|---|
| External surface | 2,583.7 m² |
| Inner volume | 391.7 dm³ |
| Fin material | Aluminium |
| Net weight | 3,001 kg |
| Quantity | 10 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 28,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 100.3 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-t-2x591GC1-B04T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 637.40 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1059.01 | 637.13 | not rated | not rated | not rated | not rated |
| 45 | 1468.55 | 1054.99 | 636.73 | not rated | not rated | not rated |
| 50 | 1873.99 | 1461.17 | 1051.61 | 636.77 | not rated | not rated |
| 55 | 2277.51 | 1863.38 | 1454.93 | 1049.13 | 637.33 | not rated |
| 60 | 2679.97 | 2263.76 | 1854.41 | 1450.20 | 1047.92 | 638.62 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 494.21 | not rated | not rated | not rated | not rated | not rated |
| 40 | 811.74 | 493.92 | not rated | not rated | not rated | not rated |
| 45 | 1119.19 | 808.50 | 493.70 | not rated | not rated | not rated |
| 50 | 1423.34 | 1113.40 | 805.85 | 493.75 | not rated | not rated |
| 55 | 1725.96 | 1415.13 | 1108.63 | 804.02 | 494.26 | not rated |
| 60 | 2027.72 | 1715.39 | 1408.34 | 1105.16 | 803.27 | 495.47 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1059.014 | 183.67 | 117.0 |
| Low speed (Y) | 811.740 | 140.80 | 73.1 |
| A | 2910 mm |
|---|---|
| B | 2400 mm |
| C | 6450 mm |
| F | 2330 mm |
| G | 7050 mm |
| E1 | 1250 mm |
| E2 | 3600 mm |
| H | 6700 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 7050 mm |
|---|---|
| Width | 2400 mm |
| Height | 2910 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.