BE-2x980AD5-B01C C
1288.81 kW
Defrost: None
Product code: BE-2x980EB1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 374,395 m³/h |
|---|---|
| External surface | 4,294.0 m² |
| Inner volume | 862.8 dm³ |
| Fin material | Aluminium |
| Net weight | 5,291 kg |
| Quantity | 18 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 32,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 94.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x980EB1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 758.13 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1283.23 | 758.55 | not rated | not rated | not rated | not rated |
| 45 | 1795.93 | 1279.87 | 758.90 | not rated | not rated | not rated |
| 50 | 2304.54 | 1789.09 | 1277.05 | 759.48 | not rated | not rated |
| 55 | 2811.01 | 2294.11 | 1783.15 | 1274.93 | 760.36 | not rated |
| 60 | 3316.64 | 2797.45 | 2285.34 | 1778.53 | 1273.93 | 761.85 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 600.28 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1006.71 | 600.40 | not rated | not rated | not rated | not rated |
| 45 | 1402.82 | 1003.75 | 600.57 | not rated | not rated | not rated |
| 50 | 1795.39 | 1396.96 | 1001.25 | 600.87 | not rated | not rated |
| 55 | 2186.34 | 1786.78 | 1392.02 | 999.45 | 601.59 | not rated |
| 60 | 2576.39 | 2175.04 | 1779.54 | 1388.35 | 998.69 | 602.81 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1283.226 | 222.71 | 84.2 |
| Low speed (Y) | 1006.714 | 174.58 | 54.6 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 11250 mm |
| F | 2330 mm |
| G | 11850 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| E3 | 3600 mm |
| H | 11500 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 11850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.