Product code: BE-2x980AD5-B01C C

Heat rejection i
1288.81 kW
Air flow
354,098 m³/h
Fans
18 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 354,098 m³/h
External surface 5,479.9 m²
Inner volume 782.0 dm³
Fin materialAluminium
Net weight 5,218 kg
Fans
Quantity 18
Diameter 800 mm
Speed 900 rpm
Power 32,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 94.0 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x980AD5-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1288.810 kW Fluid flow 223.67 m³/h Pressure drop 26.7 kPa
Heat rejection · Low speed (Y)
995.964 kW Fluid flow 172.74 m³/h Pressure drop 16.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 750.44 not rated not rated not rated not rated not rated
40 1288.81 753.67 not rated not rated not rated not rated
45 1810.34 1287.26 756.45 not rated not rated not rated
50 2326.50 1804.77 1285.85 759.04 not rated not rated
55 2840.10 2317.21 1800.18 1285.33 761.88 not rated
60 3352.27 2827.24 2309.57 1797.08 1285.88 765.16

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 585.98 not rated not rated not rated not rated not rated
40 995.96 588.32 not rated not rated not rated not rated
45 1391.42 994.13 590.33 not rated not rated not rated
50 1782.10 1386.29 992.72 592.28 not rated not rated
55 2170.57 1773.93 1382.15 992.01 594.43 not rated
60 2557.80 2159.48 1767.27 1379.32 992.31 597.08

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1288.810 223.67 26.7
Low speed (Y) 995.964 172.74 16.7

Dimensions

Dimension drawing of BE-2x980AD5-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 11250 mm
F 2230 mm
G 11850 mm
E1 1250 mm
E2 2400 mm
E3 3600 mm
H 11500 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 11850 mm
Width 2300 mm
Height 2453 mm

Downloads