Dry cooler BE-480FD1-B01 C

Dry cooler BE-480FD1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-480FD1-B01 C

Heat rejection i
412.87 kW
Air flow
88,281 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 88,281 m³/h
External surface 3,574.2 m²
Inner volume 644.5 dm³
Fin materialAluminium
Net weight 2,206 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 53.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BE-480FD1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
412.870 kW Fluid flow 71.61 m³/h Pressure drop 73.8 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
310.281 kW Fluid flow 53.82 m³/h Pressure drop 44.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 261.11 not rated not rated not rated not rated not rated
40 412.87 259.28 not rated not rated not rated not rated
45 560.48 409.19 257.66 not rated not rated not rated
50 706.80 555.10 405.97 256.33 not rated not rated
55 852.55 699.78 550.40 403.30 255.35 not rated
60 997.99 843.90 693.64 546.51 401.31 254.85

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 198.01 not rated not rated not rated not rated not rated
40 310.28 196.52 not rated not rated not rated not rated
45 419.57 307.38 195.21 not rated not rated not rated
50 527.95 415.39 304.85 194.13 not rated not rated
55 635.95 522.53 411.74 302.76 193.35 not rated
60 743.74 629.31 517.82 408.74 301.22 192.94

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 412.870 71.61 73.8
Low speed (Y) 310.281 53.82 44.4

Dimensions

Dimension drawing of BE-480FD1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 10060 mm
F 1050 mm
G 10660 mm
E1 2430 mm
E2 2400 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 10660 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.