BE-t-2x380GB5-B01T C
412.87 kW
Defrost: None
Product code: BE-580EC1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 102,966 m³/h |
|---|---|
| External surface | 1,787.1 m² |
| Inner volume | 339.5 dm³ |
| Fin material | Aluminium |
| Net weight | 1,567 kg |
| Quantity | 5 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 9,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-580EC1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 249.55 | not rated | not rated | not rated | not rated | not rated |
| 40 | 412.66 | 249.15 | not rated | not rated | not rated | not rated |
| 45 | 571.36 | 410.81 | 248.74 | not rated | not rated | not rated |
| 50 | 728.57 | 568.17 | 409.22 | 248.51 | not rated | not rated |
| 55 | 885.09 | 724.10 | 565.44 | 407.99 | 248.51 | not rated |
| 60 | 1041.22 | 879.35 | 720.26 | 563.30 | 407.25 | 248.80 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 192.89 | not rated | not rated | not rated | not rated | not rated |
| 40 | 315.77 | 192.51 | not rated | not rated | not rated | not rated |
| 45 | 435.05 | 314.25 | 192.21 | not rated | not rated | not rated |
| 50 | 553.13 | 432.49 | 312.97 | 192.02 | not rated | not rated |
| 55 | 670.66 | 549.58 | 430.33 | 312.00 | 192.01 | not rated |
| 60 | 787.89 | 666.14 | 546.57 | 428.66 | 311.45 | 192.26 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 412.655 | 71.57 | 69.6 |
| Low speed (Y) | 315.772 | 54.76 | 43.2 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 6460 mm |
| F | 1050 mm |
| G | 7060 mm |
| E1 | 1230 mm |
| E2 | 1200 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 7060 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.