BE-480FD1-B01 C
412.87 kW
Defrost: None
Product code: BE-t-2x380GB5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 125,548 m³/h |
|---|---|
| External surface | 902.8 m² |
| Inner volume | 157.8 dm³ |
| Fin material | Aluminium |
| Net weight | 1,701 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-t-2x380GB5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 240.92 | not rated | not rated | not rated | not rated | not rated |
| 40 | 412.87 | 241.48 | not rated | not rated | not rated | not rated |
| 45 | 580.60 | 412.14 | 241.95 | not rated | not rated | not rated |
| 50 | 746.92 | 578.71 | 411.53 | 242.43 | not rated | not rated |
| 55 | 912.61 | 743.92 | 577.09 | 411.10 | 242.96 | not rated |
| 60 | 1077.92 | 908.53 | 741.36 | 575.86 | 410.96 | 243.64 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 192.46 | not rated | not rated | not rated | not rated | not rated |
| 40 | 326.91 | 192.85 | not rated | not rated | not rated | not rated |
| 45 | 457.61 | 326.20 | 193.19 | not rated | not rated | not rated |
| 50 | 587.13 | 455.93 | 325.59 | 193.47 | not rated | not rated |
| 55 | 716.09 | 584.55 | 454.51 | 325.05 | 193.85 | not rated |
| 60 | 844.73 | 712.62 | 582.33 | 453.30 | 324.84 | 194.36 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 412.867 | 71.65 | 68.8 |
| Low speed (Y) | 326.905 | 56.73 | 45.4 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 3750 mm |
| F | 2330 mm |
| G | 4350 mm |
| E1 | 1150 mm |
| E2 | 1100 mm |
| H | 4000 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4350 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.