Dry cooler BE-891AB5-B04 C

Dry cooler BE-891AB5-B04 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-891AB5-B04 C

Heat rejection i
607.05 kW
Air flow
227,328 m³/h
Fans
8 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • D
    Number of fans per row: 8 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)

Data

Coil
Air flow 227,328 m³/h
External surface 1,910.3 m²
Inner volume 292.0 dm³
Fin materialAluminium
Net weight 2,161 kg
Fans
Quantity 8
Diameter 910 mm
Speed 840 rpm
Power 22,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 99.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BE-891AB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
607.052 kW Fluid flow 105.36 m³/h Pressure drop 25.1 kPa
Heat rejection · Low speed (Y)
497.578 kW Fluid flow 86.36 m³/h Pressure drop 17.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 341.51 not rated not rated not rated not rated not rated
40 607.05 343.91 not rated not rated not rated not rated
45 866.57 607.57 345.92 not rated not rated not rated
50 1124.21 865.50 608.01 347.72 not rated not rated
55 1380.95 1121.65 864.63 608.52 349.45 not rated
60 1637.24 1376.95 1119.45 864.03 609.29 351.17

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 281.82 not rated not rated not rated not rated not rated
40 497.58 283.74 not rated not rated not rated not rated
45 707.64 497.76 285.35 not rated not rated not rated
50 915.93 706.41 497.92 286.79 not rated not rated
55 1123.38 913.38 705.37 498.19 288.19 not rated
60 1330.39 1119.56 911.21 704.69 498.72 289.61

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 607.052 105.36 25.1
Low speed (Y) 497.578 86.36 17.6

Dimensions

Dimension drawing of BE-891AB5-B04 C
Dimension drawing
Dimensions as drawn
A 1958 mm
B 1300 mm
C 10060 mm
F 1150 mm
G 10660 mm
E1 1230 mm
E2 1200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10660 mm
Width 1300 mm
Height 1958 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.