BE-180CD1-B01 C
102.11 kW
Defrost: None
Product code: BE-t-180HC1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 21,838 m³/h |
|---|---|
| External surface | 423.0 m² |
| Inner volume | 50.2 dm³ |
| Fin material | Aluminium |
| Net weight | 404 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BE-t-180HC1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 63.55 | not rated | not rated | not rated | not rated | not rated |
| 40 | 101.47 | 63.20 | not rated | not rated | not rated | not rated |
| 45 | 138.18 | 100.64 | 62.89 | not rated | not rated | not rated |
| 50 | 174.51 | 136.92 | 99.90 | 62.63 | not rated | not rated |
| 55 | 210.66 | 172.83 | 135.81 | 99.30 | 62.46 | not rated |
| 60 | 246.73 | 208.58 | 171.37 | 134.90 | 98.86 | 62.38 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 48.34 | not rated | not rated | not rated | not rated | not rated |
| 40 | 76.38 | 48.05 | not rated | not rated | not rated | not rated |
| 45 | 103.51 | 75.71 | 47.79 | not rated | not rated | not rated |
| 50 | 130.37 | 102.52 | 75.13 | 47.55 | not rated | not rated |
| 55 | 157.12 | 129.07 | 101.66 | 74.61 | 47.40 | not rated |
| 60 | 183.80 | 155.51 | 127.94 | 100.90 | 74.26 | 47.34 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 101.470 | 17.60 | 85.0 |
| Low speed (Y) | 76.380 | 13.25 | 51.4 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 2260 mm |
| F | 1050 mm |
| G | 2860 mm |
| E1 | 1830 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2860 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.