Skip to Content

Dry cooler BE-t-180HC5-B01 C

Dry cooler BE-t-180HC5-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-180HC5-B01 C

Heat rejection i
96.32 kW
Air flow
21,960 m³/h
Fans
1 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 21,960 m³/h
External surface 358.4 m²
Inner volume 50.2 dm³
Fin materialAluminium
Net weight 395 kg
Fans
Quantity 1
Diameter 800 mm
Speed 900 rpm
Power 1,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 48.0 dB(A)
Sound power 80.0 dB(A)
Energy class D
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
BE-t-180HC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
96.323 kW Fluid flow 16.71 m³/h Pressure drop 77.6 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
73.485 kW Fluid flow 12.75 m³/h Pressure drop 48.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 59.35 not rated not rated not rated not rated not rated
40 96.32 59.11 not rated not rated not rated not rated
45 132.17 95.65 58.89 not rated not rated not rated
50 167.65 131.11 95.06 58.71 not rated not rated
55 202.96 166.22 130.18 94.57 58.59 not rated
60 238.19 201.17 164.96 129.41 94.21 58.55

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 45.75 not rated not rated not rated not rated not rated
40 73.49 45.53 not rated not rated not rated not rated
45 100.34 72.93 45.34 not rated not rated not rated
50 126.91 99.47 72.44 45.18 not rated not rated
55 153.35 125.76 98.72 72.03 45.08 not rated
60 179.73 151.92 124.75 98.10 71.74 45.04

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 96.323 16.71 77.6
Low speed (Y) 73.485 12.75 48.0

Dimensions

Dimension drawing of BE-t-180HC5-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 2260 mm
F 1050 mm
G 2860 mm
E1 1830 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 2860 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.