BE-580AB5-B01 C
330.77 kW
Defrost: None
Product code: BE-t-2x280HB5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 88,415 m³/h |
|---|---|
| External surface | 984.9 m² |
| Inner volume | 152.7 dm³ |
| Fin material | Aluminium |
| Net weight | 1,501 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-t-2x280HB5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 196.31 | not rated | not rated | not rated | not rated | not rated |
| 40 | 330.46 | 196.28 | not rated | not rated | not rated | not rated |
| 45 | 460.89 | 329.11 | 196.22 | not rated | not rated | not rated |
| 50 | 590.07 | 458.36 | 327.91 | 196.19 | not rated | not rated |
| 55 | 718.68 | 586.42 | 456.15 | 326.93 | 196.24 | not rated |
| 60 | 846.96 | 713.94 | 583.23 | 454.32 | 326.27 | 196.47 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 155.24 | not rated | not rated | not rated | not rated | not rated |
| 40 | 258.99 | 155.14 | not rated | not rated | not rated | not rated |
| 45 | 359.55 | 257.76 | 154.97 | not rated | not rated | not rated |
| 50 | 459.05 | 357.34 | 256.66 | 154.88 | not rated | not rated |
| 55 | 558.07 | 455.91 | 355.39 | 255.77 | 154.89 | not rated |
| 60 | 656.82 | 554.02 | 453.16 | 353.80 | 255.16 | 155.05 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 330.457 | 57.31 | 54.4 |
| Low speed (Y) | 258.989 | 44.92 | 35.2 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 4050 mm |
| F | 2330 mm |
| G | 4650 mm |
| E1 | 1850 mm |
| H | 4300 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 4650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.