BE-2x480CC1-B01C C
731.41 kW
Defrost: None
Product code: BE-t-2x580GC5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 194,066 m³/h |
|---|---|
| External surface | 1,693.4 m² |
| Inner volume | 273.2 dm³ |
| Fin material | Aluminium |
| Net weight | 2,474 kg |
| Quantity | 10 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 18,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-t-2x580GC5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 433.37 | not rated | not rated | not rated | not rated | not rated |
| 40 | 729.09 | 433.93 | not rated | not rated | not rated | not rated |
| 45 | 1016.76 | 727.33 | 434.41 | not rated | not rated | not rated |
| 50 | 1301.71 | 1012.92 | 725.88 | 435.03 | not rated | not rated |
| 55 | 1585.41 | 1295.95 | 1009.80 | 724.99 | 435.89 | not rated |
| 60 | 1868.40 | 1577.74 | 1291.15 | 1007.55 | 724.81 | 437.16 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 337.18 | not rated | not rated | not rated | not rated | not rated |
| 40 | 561.06 | 337.31 | not rated | not rated | not rated | not rated |
| 45 | 778.19 | 559.36 | 337.58 | not rated | not rated | not rated |
| 50 | 993.04 | 774.80 | 557.98 | 337.94 | not rated | not rated |
| 55 | 1206.84 | 988.06 | 772.02 | 557.08 | 338.53 | not rated |
| 60 | 1420.05 | 1200.31 | 983.95 | 770.04 | 556.86 | 339.53 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 729.093 | 126.45 | 78.7 |
| Low speed (Y) | 561.063 | 97.31 | 49.4 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 5950 mm |
| F | 2230 mm |
| G | 6550 mm |
| E1 | 1150 mm |
| E2 | 3300 mm |
| H | 6200 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 6550 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.