Compressor rack BKMR-2P-4HE-25Y

Compressor rack BKMR-2P-4HE-25Y
Illustrative photo

Producer: Albassem BRI · Line: Khufu ModularRack HT

Product code: BKMR-2P-4HE-25Y

Refrigerating capacity i
122.30 kW
Absorbed power
38.70 kW
COP
3.16
Compressors
2 × semi-hermetic reciprocating compressors
Receiver
60 l

Nominal conditions: evaporating 2 °C, condensing 45 °C (dew points), superheat 10 K, subcooling 3 K; refrigerant R404A where rated.

Model nomenclature

How to read the code of this model.

  • A
    Series: BKMR — Khufu ModularRack
  • B
    Number of compressors: 2 — Number of identical compressors on the rack (2 to 6).
  • C
    Application: P — Medium / high temperature
  • D
    Compressor model: 4HE-25Y — Model of the compressors fitted (all compressors of a rack are the same model); an 'EVI' tail marks enhanced vapour injection.

Data

Rack
ApplicationHigh temperature (HT)
Compressors2 × semi-hermetic reciprocating compressors
Liquid receiver 60 l
Net weight 630 kg
Electrical
Max. current 77.6 A
Starting current 249.8 A
Connections
Suction 2"5/8
Liquid 1"1/8
Discharge 1"5/8
Liquid set
L / W / H 666/402/1366 mm
Weight 90 kg

Performance

Evaporating temperature -50…5 °C, condensing temperature 20…55 °C (dew points); superheat 10 K, subcooling 3 K.

R404A, evaporating 2 °C, condensing 45 °C (dew points; superheat 10 K, subcooling 3 K)

Refrigerating capacity
122.30 kW
Absorbed power
38.70 kW
COP
3.16
Current
66.6 A
Heat rejection
161.00 kW

Heat rejection = refrigerating capacity + absorbed power. COP = refrigerating capacity / absorbed power.

Standard points

Te [°C] Tc [°C] Refrigerating capacity [kW] Absorbed power [kW] COP Current [A]
2 45 122.30 38.70 3.16 66.6

Evaporating × condensing temperature (dew points)

R404A; rows: condensing temperature Tc [°C]; columns: evaporating temperature Te [°C]. The highlighted cell is the nominal point. "—": outside the compressors' operating envelope.

Capacity [kW]

Capacity [kW]: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -40-35-30-25-20-15-10-505
20 25.20 34.20 45.10 58.00 73.40 91.40 112.50 137.10 165.90 not rated
25 22.70 31.00 41.10 53.20 67.70 84.70 104.80 128.30 155.80 188.00
30 20.00 27.70 37.10 48.40 62.00 78.00 97.00 119.30 145.50 175.90
35 17.30 24.40 33.10 43.60 56.20 71.30 89.10 110.10 134.80 163.50
40 14.70 21.20 29.10 38.80 50.50 64.50 81.10 100.80 123.80 150.80
45 12.30 18.00 25.20 34.00 44.80 57.60 73.00 91.20 112.70 137.80
50 10.00 15.00 21.40 29.30 39.00 50.80 64.80 81.60 101.30 124.60
55 7.90 12.20 17.70 24.70 33.30 43.90 56.60 71.80 89.80 111.10

Power [kW]

Power [kW]: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -40-35-30-25-20-15-10-505
20 13.60 15.60 17.60 19.40 21.00 22.30 23.40 24.00 24.30 not rated
25 13.90 16.10 18.30 20.40 22.30 24.10 25.50 26.70 27.40 27.70
30 14.00 16.40 18.90 21.30 23.60 25.70 27.50 29.10 30.30 31.10
35 14.00 16.70 19.40 22.00 24.60 27.10 29.30 31.30 33.00 34.30
40 14.00 16.80 19.70 22.60 25.50 28.30 30.90 33.40 35.50 37.30
45 13.80 16.80 19.90 23.10 26.30 29.40 32.40 35.20 37.70 40.00
50 13.50 16.70 20.00 23.40 26.90 30.30 33.60 36.80 39.80 42.40
55 13.10 16.40 19.90 23.60 27.30 31.00 34.70 38.20 41.60 44.70

COP

COP: Evaporating × condensing temperature (dew points)
Tc \ Te [°C] -40-35-30-25-20-15-10-505
20 1.85 2.19 2.56 2.99 3.50 4.10 4.81 5.71 6.83 not rated
25 1.63 1.93 2.25 2.61 3.04 3.51 4.11 4.81 5.69 6.79
30 1.43 1.69 1.96 2.27 2.63 3.04 3.53 4.10 4.80 5.66
35 1.24 1.46 1.71 1.98 2.28 2.63 3.04 3.52 4.08 4.77
40 1.05 1.26 1.48 1.72 1.98 2.28 2.62 3.02 3.49 4.04
45 0.89 1.07 1.27 1.47 1.70 1.96 2.25 2.59 2.99 3.44
50 0.74 0.90 1.07 1.25 1.45 1.68 1.93 2.22 2.55 2.94
55 0.60 0.74 0.89 1.05 1.22 1.42 1.63 1.88 2.16 2.49

Dimensions

Dimension drawing of BKMR-2P-4HE-25Y
Dimension drawing
Dimensions as drawn
L 1915 mm
P 800 mm
H 1500 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.