BKMR-2P-V25-71Y-F-B
114.98 kW
Defrost: None
Product code: BKMR-2P-V25-71Y-F-C
Nominal conditions: evaporating 2 °C, condensing 45 °C (dew points), superheat 10 K, subcooling 3 K; refrigerant R404A where rated.
| Application | High temperature (HT) |
|---|---|
| Compressors | 2 × semi-hermetic reciprocating compressors |
| Liquid receiver | 60 l |
| Net weight | 635 kg |
| Max. current | 87.0 A |
|---|---|
| Starting current | 161.8 A |
| Suction | 2"5/8 |
|---|---|
| Liquid | 1"1/8 |
| Discharge | 1"5/8 |
| L / W / H | 666/402/1366 mm |
|---|---|
| Weight | 90 kg |
Evaporating temperature -50…5 °C, condensing temperature 20…55 °C (dew points); superheat 10 K, subcooling 3 K.
R404A, evaporating 2 °C, condensing 45 °C (dew points; superheat 10 K, subcooling 3 K)
Heat rejection = refrigerating capacity + absorbed power. COP = refrigerating capacity / absorbed power.
| Te [°C] | Tc [°C] | Refrigerating capacity [kW] | Absorbed power [kW] | COP | Current [A] |
|---|---|---|---|---|---|
| 2 | 45 | 114.98 | 38.23 | 3.01 | 68.2 |
R404A; rows: condensing temperature Tc [°C]; columns: evaporating temperature Te [°C]. The highlighted cell is the nominal point. "—": outside the compressors' operating envelope.
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 5 |
|---|---|---|---|---|---|---|---|---|---|---|
| 20 | 23.17 | 31.31 | 41.51 | 54.06 | 69.26 | 87.40 | 108.76 | 133.61 | 162.17 | not rated |
| 25 | 20.53 | 28.17 | 37.70 | 49.40 | 63.56 | 80.49 | 100.47 | 123.78 | 150.68 | 181.36 |
| 30 | 17.94 | 25.10 | 33.96 | 44.81 | 57.95 | 73.67 | 92.28 | 114.07 | 139.31 | 168.22 |
| 35 | 15.41 | 22.09 | 30.29 | 40.30 | 52.42 | 66.94 | 84.19 | 104.46 | 128.05 | 155.21 |
| 40 | 12.96 | 19.16 | 26.70 | 35.88 | 46.98 | 60.32 | 76.21 | 94.98 | 116.92 | 142.33 |
| 45 | 10.58 | 16.30 | 23.20 | 31.55 | 41.65 | 53.81 | 68.36 | 85.62 | 105.93 | 129.61 |
| 50 | not rated | not rated | 19.78 | 27.31 | 36.42 | 47.42 | 60.64 | 76.42 | 95.11 | 117.08 |
| 55 | not rated | not rated | not rated | not rated | 31.33 | 41.17 | 53.08 | 67.40 | 84.50 | 104.80 |
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 5 |
|---|---|---|---|---|---|---|---|---|---|---|
| 20 | 13.25 | 15.30 | 17.33 | 19.28 | 21.06 | 22.61 | 23.86 | 24.73 | 25.16 | not rated |
| 25 | 13.55 | 15.79 | 18.05 | 20.25 | 22.34 | 24.23 | 25.86 | 27.15 | 28.03 | 28.43 |
| 30 | 13.74 | 16.15 | 18.62 | 21.08 | 23.45 | 25.67 | 27.66 | 29.36 | 30.68 | 31.56 |
| 35 | 13.84 | 16.41 | 19.07 | 21.77 | 24.41 | 26.94 | 29.28 | 31.36 | 33.10 | 34.45 |
| 40 | 13.84 | 16.55 | 19.40 | 22.31 | 25.21 | 28.03 | 30.70 | 33.15 | 35.31 | 37.10 |
| 45 | 13.74 | 16.58 | 19.59 | 22.71 | 25.85 | 28.95 | 31.94 | 34.74 | 37.30 | 39.52 |
| 50 | not rated | not rated | 19.67 | 22.97 | 26.34 | 29.70 | 32.99 | 36.14 | 39.07 | 41.71 |
| 55 | not rated | not rated | not rated | not rated | 26.67 | 30.28 | 33.86 | 37.33 | 40.62 | 43.66 |
| Tc \ Te [°C] | -40 | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 5 |
|---|---|---|---|---|---|---|---|---|---|---|
| 20 | 1.75 | 2.05 | 2.39 | 2.80 | 3.29 | 3.87 | 4.56 | 5.40 | 6.45 | not rated |
| 25 | 1.52 | 1.78 | 2.09 | 2.44 | 2.85 | 3.32 | 3.89 | 4.56 | 5.38 | 6.38 |
| 30 | 1.31 | 1.55 | 1.82 | 2.13 | 2.47 | 2.87 | 3.34 | 3.89 | 4.54 | 5.33 |
| 35 | 1.11 | 1.35 | 1.59 | 1.85 | 2.15 | 2.49 | 2.88 | 3.33 | 3.87 | 4.51 |
| 40 | 0.94 | 1.16 | 1.38 | 1.61 | 1.86 | 2.15 | 2.48 | 2.86 | 3.31 | 3.84 |
| 45 | 0.77 | 0.98 | 1.18 | 1.39 | 1.61 | 1.86 | 2.14 | 2.46 | 2.84 | 3.28 |
| 50 | not rated | not rated | 1.01 | 1.19 | 1.38 | 1.60 | 1.84 | 2.11 | 2.43 | 2.81 |
| 55 | not rated | not rated | not rated | not rated | 1.17 | 1.36 | 1.57 | 1.81 | 2.08 | 2.40 |
| L | 1915 mm |
|---|---|
| P | 800 mm |
| H | 1500 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.