BHSR-5P-ZB95
105.90 kW
Defrost: None
Product code: BHSR-6P-ZB76
Nominal conditions: evaporating -10 °C, condensing 45 °C (dew points), superheat 10 K, subcooling 3 K; refrigerant R404A where rated.
| Application | Medium temperature (MT) |
|---|---|
| Compressors | 6 × scroll compressors |
| Liquid receiver | 120 l |
| Net weight | 980 kg |
| Max. current | 108.0 A |
|---|---|
| Starting current | 208.0 A |
| Suction | 3"1/8 |
|---|---|
| Liquid | 1"3/8 |
| Discharge | 2"1/8 |
| L / W / H | 714/455/1834 mm |
|---|---|
| Weight | 130 kg |
Evaporating temperature -50…5 °C, condensing temperature 20…55 °C (dew points); superheat 10 K, subcooling 3 K.
R404A, evaporating -10 °C, condensing 45 °C (dew points; superheat 10 K, subcooling 3 K)
Heat rejection = refrigerating capacity + absorbed power. COP = refrigerating capacity / absorbed power.
| Te [°C] | Tc [°C] | Refrigerating capacity [kW] | Absorbed power [kW] | COP | Current [A] |
|---|---|---|---|---|---|
| -10 | 40 | 114.30 | 44.00 | 2.60 | 84.5 |
| -10 | 45 | 104.50 | 48.90 | 2.14 | 90.6 |
R404A; rows: condensing temperature Tc [°C]; columns: evaporating temperature Te [°C]. The highlighted cell is the nominal point. "—": outside the compressors' operating envelope.
| Tc \ Te [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 |
|---|---|---|---|---|---|---|---|
| 20 | 78.60 | 98.00 | 121.20 | 148.70 | 180.90 | 218.30 | not rated |
| 25 | 74.20 | 92.70 | 114.70 | 140.70 | 171.10 | 206.30 | 246.70 |
| 30 | 69.40 | 87.00 | 107.80 | 132.30 | 160.90 | 194.00 | 232.10 |
| 35 | 64.00 | 80.80 | 100.50 | 123.50 | 150.30 | 181.40 | 217.20 |
| 40 | 58.10 | 74.10 | 92.70 | 114.30 | 139.40 | 168.50 | 202.00 |
| 45 | 51.40 | 66.70 | 84.30 | 104.50 | 127.90 | 155.10 | 186.40 |
| 50 | not rated | 58.70 | 75.20 | 94.10 | 115.90 | 141.20 | 170.40 |
| 55 | not rated | 50.00 | 65.60 | 83.20 | 103.40 | 126.80 | 154.00 |
| Tc \ Te [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 |
|---|---|---|---|---|---|---|---|
| 20 | 27.70 | 28.30 | 28.90 | 29.50 | 30.10 | 30.70 | not rated |
| 25 | 30.70 | 31.40 | 31.90 | 32.50 | 33.00 | 33.60 | 34.20 |
| 30 | 34.20 | 34.80 | 35.30 | 35.80 | 36.30 | 36.90 | 37.40 |
| 35 | 38.10 | 38.60 | 39.20 | 39.60 | 40.10 | 40.50 | 41.00 |
| 40 | 42.50 | 43.10 | 43.50 | 44.00 | 44.40 | 44.70 | 45.10 |
| 45 | 47.60 | 48.10 | 48.50 | 48.90 | 49.20 | 49.50 | 49.80 |
| 50 | not rated | 53.80 | 54.20 | 54.50 | 54.70 | 54.90 | 55.10 |
| 55 | not rated | 60.30 | 60.60 | 60.80 | 61.00 | 61.10 | 61.20 |
| Tc \ Te [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 |
|---|---|---|---|---|---|---|---|
| 20 | 2.84 | 3.46 | 4.19 | 5.04 | 6.01 | 7.11 | not rated |
| 25 | 2.42 | 2.95 | 3.60 | 4.33 | 5.18 | 6.14 | 7.21 |
| 30 | 2.03 | 2.50 | 3.05 | 3.70 | 4.43 | 5.26 | 6.21 |
| 35 | 1.68 | 2.09 | 2.56 | 3.12 | 3.75 | 4.48 | 5.30 |
| 40 | 1.37 | 1.72 | 2.13 | 2.60 | 3.14 | 3.77 | 4.48 |
| 45 | 1.08 | 1.39 | 1.74 | 2.14 | 2.60 | 3.13 | 3.74 |
| 50 | not rated | 1.09 | 1.39 | 1.73 | 2.12 | 2.57 | 3.09 |
| 55 | not rated | 0.83 | 1.08 | 1.37 | 1.70 | 2.08 | 2.52 |
| Length | 3715 mm |
|---|---|
| Width | 800 mm |
| Height | 1500 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.