EA-DA-x-150BE7-B22 C
9.10 kW
Defrost: Electric
Product code: EA-DA-x-335BE7-B21 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,121 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 38.0 m² |
| Inner volume | 14.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 102 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 495 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø19 |
| EA-DA-x-335BE7-B21 C | None |
|---|---|
| EA-DA-x-335BE7-B21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | 3.39 | 3.73 | 4.04 | 4.26 | 4.40 | 4.44 | 4.57 | 4.88 | 5.32 | 5.22 | 5.18 | 5.13 | 5.05 |
| 5 | not rated | not rated | 4.51 | 4.94 | 5.20 | 5.44 | 5.59 | 5.78 | 6.18 | 6.77 | 6.66 | 6.62 | 6.54 | 6.41 |
| 6 | not rated | not rated | 4.85 | ≈ 5.64 | 6.09 | 6.44 | 6.67 | 6.92 | 7.40 | 8.12 | 8.00 | 7.95 | 7.85 | 7.67 |
| 7 | 1.75 | ≈ 1.72 | ≈ 4.59 | ≈ 6.35 | 6.93 | 7.39 | 7.72 | 8.03 | 8.60 | 9.45 | 9.34 | 9.28 | 9.17 | 8.94 |
| 8 | 1.95 | ≈ 1.91 | ≈ 3.32 | ≈ 6.99 | 7.70 | 8.28 | 8.71 | 9.11 | 9.77 | 10.75 | 10.67 | 10.61 | 10.48 | 10.23 |
| 9 | 2.14 | 2.11 | ≈ 2.11 | ≈ 7.58 | 8.40 | 9.11 | 9.66 | 10.15 | 10.91 | 12.03 | 11.99 | 11.92 | 11.79 | 11.51 |
| 10 | 2.33 | 2.30 | ≈ 2.30 | ≈ 4.27 | ≈ 9.06 | 9.90 | 10.57 | 11.16 | 12.02 | 13.28 | 13.28 | 13.22 | 13.10 | 12.80 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.275 |
| SC2 | 0 | 8 | 9.107 |
| SC3 | -18 | 7 | 6.592 |
| SC4 | -25 | 6 | 4.845 |
| SC5 | -34 | 6 | — |
| A | 1957 mm |
|---|---|
| B | 730 mm |
| C | 530 mm |
| F | 560 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø19 |
| Length | 1957 mm |
|---|---|
| Width | 730 mm |
| Height | 530 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.