EA-DA-245AE7-C23 C
16.07 kW
Defrost: None
Product code: EA-DA-x-535BE7-B21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 10,202 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 63.1 m² |
| Inner volume | 22.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 155 kg |
| Quantity | 5 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 825 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 77.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø22 |
| EA-DA-x-535BE7-B21 C | None |
|---|---|
| EA-DA-x-535BE7-B21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | 5.78 | 6.32 | 6.80 | 7.13 | 7.33 | 7.39 | 7.63 | 8.10 | 8.82 | 8.63 | 8.57 | 8.47 | 8.33 |
| 5 | not rated | 6.92 | 7.67 | 8.18 | 8.75 | 9.11 | 9.33 | 9.63 | 10.29 | 11.25 | 11.06 | 10.97 | 10.84 | 10.61 |
| 6 | not rated | not rated | 8.40 | 9.57 | 10.28 | 10.81 | 11.17 | 11.55 | 12.34 | 13.51 | 13.30 | 13.20 | 13.04 | 12.72 |
| 7 | ≈ 2.90 | ≈ 3.39 | ≈ 9.69 | 10.79 | 11.72 | 12.44 | 12.94 | 13.42 | 14.37 | 15.76 | 15.55 | 15.44 | 15.24 | 14.84 |
| 8 | 3.23 | ≈ 3.17 | ≈ 6.77 | ≈ 11.91 | 13.05 | 13.97 | 14.64 | 15.26 | 16.35 | 17.96 | 17.79 | 17.66 | 17.44 | 16.99 |
| 9 | 3.55 | 3.50 | ≈ 3.29 | ≈ 12.93 | 14.28 | 15.41 | 16.27 | 17.04 | 18.29 | 20.13 | 20.00 | 19.88 | 19.64 | 19.15 |
| 10 | 3.87 | 3.81 | ≈ 3.81 | ≈ 12.45 | ≈ 15.42 | 16.77 | 17.82 | 18.76 | 20.17 | 22.24 | 22.18 | 22.07 | 21.83 | 21.31 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 22.182 |
| SC2 | 0 | 8 | 15.258 |
| SC3 | -18 | 7 | 11.185 |
| SC4 | -25 | 6 | 8.402 |
| SC5 | -34 | 6 | — |
| A | 2957 mm |
|---|---|
| B | 730 mm |
| C | 530 mm |
| F | 560 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 2535 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø22 |
| Length | 2957 mm |
|---|---|
| Width | 730 mm |
| Height | 530 mm |
Our engineers answer with a selection for your conditions.