EA-DV-263GC10-A13 C
33.17 kW
Defrost: None
Product code: EA-DV-163GE4-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 17,445 m³/h |
|---|---|
| External surface | 162.9 m² |
| Inner volume | 33.1 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 271 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 87.9 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-DV-163GE4-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 14.38 | 14.39 | 14.40 | 14.47 | 14.45 | 14.38 | 14.27 | 14.36 | 15.23 | 16.47 | 16.08 | 15.94 | 15.73 | 15.41 |
| 5 | 18.19 | 18.48 | 18.74 | 18.97 | 19.02 | 18.97 | 18.82 | 18.89 | 20.01 | 21.62 | 21.02 | 20.81 | 20.51 | 20.07 |
| 6 | 21.80 | 22.37 | 22.96 | 23.45 | 23.69 | 23.75 | 23.66 | 23.73 | 25.12 | 27.14 | 26.38 | 26.08 | 25.66 | 25.01 |
| 7 | 24.85 | 25.88 | 26.81 | 27.64 | 28.17 | 28.48 | 28.61 | 28.80 | 30.51 | 32.99 | 32.07 | 31.71 | 31.17 | 30.32 |
| 8 | 27.66 | 29.11 | 30.42 | 31.56 | 32.31 | 32.77 | 33.00 | 33.28 | 35.32 | 38.32 | 37.44 | 37.09 | 36.56 | 35.68 |
| 9 | 30.24 | 32.16 | 33.88 | 35.38 | 36.41 | 37.05 | 37.41 | 37.76 | 40.09 | 43.50 | 42.53 | 42.12 | 41.51 | 40.48 |
| 10 | 32.61 | 35.01 | 37.20 | 39.11 | 40.43 | 41.31 | 41.81 | 42.27 | 44.90 | 48.73 | 47.69 | 47.23 | 46.54 | 45.36 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.34 | 12.28 | 12.28 | 12.32 | 12.31 | 12.25 | 12.16 | 12.31 | 13.07 | 14.16 | 13.85 | 13.74 | 13.59 | 13.37 |
| 5 | 15.66 | 15.75 | 15.86 | 15.99 | 15.98 | 15.92 | 15.80 | 15.93 | 16.89 | 18.28 | 17.80 | 17.63 | 17.40 | 17.04 |
| 6 | 18.84 | 19.17 | 19.48 | 19.76 | 19.86 | 19.82 | 19.68 | 19.75 | 20.92 | 22.62 | 21.97 | 21.73 | 21.38 | 20.83 |
| 7 | 21.84 | 22.40 | 22.98 | 23.48 | 23.73 | 23.78 | 23.68 | 23.77 | 25.17 | 27.21 | 26.39 | 26.07 | 25.60 | 24.85 |
| 8 | 24.44 | 25.38 | 26.25 | 27.03 | 27.51 | 27.77 | 27.79 | 27.91 | 29.55 | 31.95 | 31.00 | 30.61 | 30.04 | 29.09 |
| 9 | 26.85 | 28.14 | 29.32 | 30.35 | 31.01 | 31.37 | 31.51 | 31.77 | 33.70 | 36.51 | 35.60 | 35.21 | 34.59 | 33.46 |
| 10 | 29.08 | 30.76 | 32.28 | 33.60 | 34.46 | 34.98 | 35.20 | 35.52 | 37.67 | 40.81 | 39.81 | 39.37 | 38.70 | 37.56 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 47.686 | 39.814 |
| SC2 | 0 | 8 | 33.276 | 27.908 |
| SC3 | -18 | 7 | 27.886 | 23.605 |
| SC4 | -25 | 6 | 22.960 | 19.483 |
| SC5 | -34 | 6 | 21.985 | 18.934 |
| A | 1725 mm |
|---|---|
| B | 1000 mm |
| C | 1260 mm |
| F | 960 mm |
| G | 1685 mm |
| E | 1335 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 1725 mm |
|---|---|
| Width | 1685 mm |
| Height | 1260 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.