EA-DV-191GE10-A04 C
32.21 kW
Defrost: None
Product code: EA-DV-163GI10-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 15,098 m³/h |
|---|---|
| External surface | 132.0 m² |
| Inner volume | 54.0 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 318 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 69.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | C |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-DV-163GI10-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 14.64 | 14.49 | 14.42 | 14.39 | 14.30 | 14.17 | 14.00 | 14.07 | 14.91 | 16.11 | 15.67 | 15.52 | 15.31 | 15.00 |
| 5 | 18.66 | 18.60 | 18.67 | 18.76 | 18.72 | 18.59 | 18.39 | 18.43 | 19.51 | 21.05 | 20.41 | 20.18 | 19.85 | 19.34 |
| 6 | 22.48 | 22.73 | 23.00 | 23.25 | 23.31 | 23.21 | 23.01 | 23.03 | 24.36 | 26.29 | 25.46 | 25.14 | 24.67 | 23.93 |
| 7 | 26.11 | 26.69 | 27.24 | 27.72 | 27.93 | 27.94 | 27.78 | 27.75 | 29.36 | 31.70 | 30.69 | 30.28 | 29.67 | 28.67 |
| 8 | 29.51 | 30.49 | 31.24 | 32.01 | 32.44 | 32.59 | 32.52 | 32.59 | 34.49 | 37.25 | 36.09 | 35.59 | 34.86 | 33.64 |
| 9 | 32.66 | 33.88 | 35.13 | 36.24 | 36.95 | 37.28 | 37.32 | 37.46 | 39.67 | 42.86 | 41.58 | 41.02 | 40.17 | 38.74 |
| 10 | 35.31 | 37.08 | 38.71 | 40.14 | 41.07 | 41.65 | 41.91 | 42.24 | 44.79 | 48.49 | 47.12 | 46.50 | 45.54 | 43.92 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.44 | 12.25 | 12.17 | 12.15 | 12.07 | 11.97 | 11.83 | 11.96 | 12.69 | 13.73 | 13.38 | 13.26 | 13.09 | 12.85 |
| 5 | 15.77 | 15.67 | 15.67 | 15.70 | 15.65 | 15.53 | 15.36 | 15.44 | 16.36 | 17.67 | 17.15 | 16.96 | 16.69 | 16.27 |
| 6 | 19.11 | 19.14 | 19.21 | 19.35 | 19.35 | 19.25 | 19.06 | 19.10 | 20.22 | 21.83 | 21.13 | 20.86 | 20.47 | 19.86 |
| 7 | 22.28 | 22.52 | 22.79 | 23.06 | 23.12 | 23.06 | 22.87 | 22.90 | 24.21 | 26.14 | 25.28 | 24.94 | 24.43 | 23.61 |
| 8 | 25.30 | 25.80 | 26.28 | 26.73 | 26.93 | 26.92 | 26.75 | 26.77 | 28.31 | 30.55 | 29.56 | 29.15 | 28.53 | 27.50 |
| 9 | 28.15 | 28.96 | 29.71 | 30.37 | 30.63 | 30.73 | 30.62 | 30.68 | 32.45 | 35.01 | 33.91 | 33.43 | 32.72 | 31.52 |
| 10 | 30.83 | 31.99 | 32.91 | 33.83 | 34.34 | 34.57 | 34.53 | 34.64 | 36.64 | 39.54 | 38.34 | 37.81 | 36.99 | 35.62 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 47.116 | 38.344 |
| SC2 | 0 | 8 | 32.592 | 26.774 |
| SC3 | -18 | 7 | 27.830 | 23.111 |
| SC4 | -25 | 6 | 22.995 | 19.208 |
| SC5 | -34 | 6 | 22.562 | 19.140 |
| A | 1725 mm |
|---|---|
| B | 1200 mm |
| C | 1260 mm |
| F | 1160 mm |
| G | 1885 mm |
| E | 1335 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 1725 mm |
|---|---|
| Width | 1885 mm |
| Height | 1260 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.