EA-145AC7-C01 C
6.31 kW
Defrost: Electric
Product code: EA-140AG4-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,310 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 39.1 m² |
| Inner volume | 8.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 55 kg |
| Quantity | 1 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 160 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-140AG4-C01 C | None |
|---|---|
| EA-140AG4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.82 | 2.85 | 2.89 | 2.92 | 2.93 | 2.91 | 2.88 | 2.96 | 3.16 | 3.43 | 3.35 | 3.32 | 3.29 | 3.25 |
| 5 | 3.50 | 3.59 | 3.67 | 3.74 | 3.76 | 3.75 | 3.71 | 3.78 | 4.01 | 4.35 | 4.21 | 4.16 | 4.09 | 3.98 |
| 6 | 4.17 | 4.30 | 4.44 | 4.56 | 4.61 | 4.62 | 4.58 | 4.63 | 4.90 | 5.31 | 5.12 | 5.05 | 4.94 | not rated |
| 7 | 4.78 | 5.01 | 5.21 | 5.39 | 5.48 | 5.50 | 5.46 | 5.51 | 5.83 | 6.30 | 6.08 | 5.98 | 5.84 | not rated |
| 8 | 5.34 | 5.64 | 5.92 | 6.16 | 6.31 | 6.38 | 6.36 | 6.40 | 6.78 | 7.30 | 7.05 | 6.94 | not rated | not rated |
| 9 | 5.83 | 6.22 | 6.58 | 6.89 | 7.06 | 7.16 | 7.18 | 7.25 | 7.68 | 8.30 | 8.04 | 7.91 | not rated | not rated |
| 10 | 6.27 | 6.76 | 7.21 | 7.55 | 7.80 | 7.95 | 7.99 | 8.08 | 8.55 | 9.24 | 8.97 | 8.83 | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.970 |
| SC2 | 0 | 8 | 6.403 |
| SC3 | -18 | 7 | 5.431 |
| SC4 | -25 | 6 | 4.440 |
| SC5 | -34 | 6 | 4.211 |
| A | 917 mm |
|---|---|
| B | 686 mm |
| C | 605 mm |
| F | 495 mm |
| E | 585 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 917 mm |
|---|---|
| Width | 686 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.