EA-330AE10-C01 C
6.91 kW
Defrost: None
Product code: EA-145AE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,040 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 18.3 m² |
| Inner volume | 8.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 53 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 490 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-145AE10-C01 C | None |
|---|---|
| EA-145AE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.85 | 2.79 | 2.75 | 2.71 | 2.67 | 2.62 | 2.56 | 2.58 | 2.72 | 2.93 | 2.83 | 2.80 | 2.75 | 2.67 |
| 5 | 3.77 | 3.74 | 3.72 | 3.71 | 3.67 | 3.61 | 3.54 | 3.56 | 3.76 | 4.05 | 3.91 | 3.86 | 3.80 | 3.71 |
| 6 | 4.67 | 4.70 | 4.74 | 4.76 | 4.75 | 4.70 | 4.62 | 4.63 | 4.89 | 5.26 | 5.07 | 5.00 | 4.91 | 4.77 |
| 7 | 5.57 | 5.67 | 5.76 | 5.83 | 5.86 | 5.83 | 5.76 | 5.77 | 6.10 | 6.57 | 6.33 | 6.24 | 6.11 | 5.90 |
| 8 | 6.39 | 6.58 | 6.76 | 6.91 | 6.99 | 6.99 | 6.94 | 6.96 | 7.36 | 7.94 | 7.66 | 7.55 | 7.38 | 7.11 |
| 9 | 7.12 | 7.40 | 7.66 | 7.90 | 8.05 | 8.13 | 8.14 | 8.18 | 8.64 | 9.33 | 9.03 | 8.90 | 8.71 | 8.39 |
| 10 | 7.78 | 8.16 | 8.50 | 8.81 | 8.98 | 9.11 | 9.16 | 9.25 | 9.82 | 10.64 | 10.38 | 10.26 | 10.06 | 9.69 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.379 |
| SC2 | 0 | 8 | 6.960 |
| SC3 | -18 | 7 | 5.848 |
| SC4 | -25 | 6 | 4.735 |
| SC5 | -34 | 6 | 4.685 |
| A | 1067 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E | 735 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1067 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.