EA-235AG8-C01 C
8.90 kW
Defrost: Electric
Product code: EA-150AC6-C09 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,931 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 24.8 m² |
| Inner volume | 7.5 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 55 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 710 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.2 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-150AC6-C09 C | None |
|---|---|
| EA-150AC6-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.52 | 3.54 | 3.56 | 3.57 | 3.55 | 3.50 | 3.45 | 3.46 | 3.65 | 3.93 | 3.80 | 3.75 | 3.68 | 3.58 |
| 5 | 4.57 | 4.69 | 4.79 | 4.85 | 4.87 | 4.85 | 4.80 | 4.82 | 5.10 | 5.49 | 5.32 | 5.26 | 5.17 | 5.04 |
| 6 | 5.50 | 5.73 | 5.94 | 6.12 | 6.24 | 6.30 | 6.27 | 6.29 | 6.66 | 7.19 | 6.97 | 6.89 | 6.77 | 6.58 |
| 7 | 6.28 | 6.63 | 6.94 | 7.17 | 7.35 | 7.46 | 7.52 | 7.61 | 8.08 | 8.78 | 8.58 | 8.51 | 8.39 | 8.21 |
| 8 | 7.00 | 7.42 | 7.84 | 8.21 | 8.47 | 8.64 | 8.74 | 8.85 | 9.41 | 10.23 | 10.01 | 9.92 | 9.79 | 9.57 |
| 9 | 7.55 | 8.19 | 8.74 | 9.22 | 9.57 | 9.81 | 9.96 | 10.11 | 10.75 | 11.70 | 11.47 | 11.37 | 11.21 | 10.95 |
| 10 | ≈ 8.18 | 8.91 | 9.59 | 10.20 | 10.65 | 10.97 | 11.18 | 11.37 | 12.10 | 13.17 | 12.93 | 12.83 | 12.65 | 12.35 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.934 |
| SC2 | 0 | 8 | 8.854 |
| SC3 | -18 | 7 | 7.248 |
| SC4 | -25 | 6 | 5.940 |
| SC5 | -34 | 6 | 5.558 |
| A | 1237 mm |
|---|---|
| B | 590 mm |
| C | 685 mm |
| F | 395 mm |
| E | 885 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1237 mm |
|---|---|
| Width | 590 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.