EA-330AE4-C05 C
7.59 kW
Defrost: Electric
Product code: EA-150AC8-C09 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,115 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 19.2 m² |
| Inner volume | 7.5 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 55 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 710 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 78.6 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-150AC8-C09 C | None |
|---|---|
| EA-150AC8-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.97 | 2.94 | 2.92 | 2.89 | 2.85 | 2.80 | 2.75 | 2.74 | 2.88 | 3.09 | 2.98 | 2.94 | 2.89 | 2.81 |
| 5 | 3.89 | 3.93 | 3.97 | 3.99 | 3.97 | 3.93 | 3.87 | 3.86 | 4.08 | 4.38 | 4.23 | 4.18 | 4.10 | 3.97 |
| 6 | 4.80 | 4.94 | 5.05 | 5.14 | 5.16 | 5.15 | 5.10 | 5.11 | 5.40 | 5.81 | 5.61 | 5.54 | 5.43 | 5.27 |
| 7 | 5.60 | 5.83 | 6.03 | 6.22 | 6.33 | 6.40 | 6.40 | 6.41 | 6.78 | 7.33 | 7.10 | 7.01 | 6.88 | 6.67 |
| 8 | 6.29 | 6.61 | 6.91 | 7.13 | 7.31 | 7.42 | 7.48 | 7.56 | 8.04 | 8.72 | 8.53 | 8.46 | 8.34 | 8.15 |
| 9 | 6.92 | 7.30 | 7.70 | 8.05 | 8.30 | 8.46 | 8.55 | 8.66 | 9.21 | 10.00 | 9.80 | 9.71 | 9.58 | 9.36 |
| 10 | 7.50 | 8.00 | 8.50 | 8.94 | 9.26 | 9.49 | 9.63 | 9.76 | 10.38 | 11.30 | 11.08 | 10.98 | 10.83 | 10.59 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.075 |
| SC2 | 0 | 8 | 7.564 |
| SC3 | -18 | 7 | 6.270 |
| SC4 | -25 | 6 | 5.050 |
| SC5 | -34 | 6 | 4.839 |
| A | 1237 mm |
|---|---|
| B | 590 mm |
| C | 685 mm |
| F | 395 mm |
| E | 885 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1237 mm |
|---|---|
| Width | 590 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.