EA-163FC10-C19 C
10.87 kW
Defrost: None
Product code: EA-150AE7-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,379 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 32.4 m² |
| Inner volume | 11.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 65 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 710 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-150AE7-C09 C | None |
|---|---|
| EA-150AE7-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.42 | 4.39 | 4.38 | 4.36 | 4.32 | 4.26 | 4.18 | 4.24 | 4.49 | 4.83 | 4.68 | 4.63 | 4.55 | 4.44 |
| 5 | 5.71 | 5.78 | 5.84 | 5.89 | 5.87 | 5.82 | 5.73 | 5.77 | 6.11 | 6.59 | 6.38 | 6.30 | 6.21 | 6.06 |
| 6 | 7.00 | 7.19 | 7.35 | 7.46 | 7.51 | 7.48 | 7.40 | 7.44 | 7.87 | 8.49 | 8.19 | 8.09 | 7.93 | 7.70 |
| 7 | 8.15 | 8.47 | 8.76 | 9.02 | 9.17 | 9.21 | 9.15 | 9.19 | 9.73 | 10.51 | 10.15 | 10.02 | 9.81 | 9.48 |
| 8 | 9.14 | 9.59 | 10.00 | 10.36 | 10.55 | 10.69 | 10.73 | 10.84 | 11.51 | 12.48 | 12.16 | 12.01 | 11.77 | 11.37 |
| 9 | 10.05 | 10.66 | 11.14 | 11.62 | 11.95 | 12.13 | 12.22 | 12.36 | 13.12 | 14.24 | 13.89 | 13.73 | 13.50 | 13.11 |
| 10 | 10.88 | 11.59 | 12.28 | 12.89 | 13.31 | 13.58 | 13.71 | 13.89 | 14.75 | 16.01 | 15.63 | 15.46 | 15.20 | 14.75 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 15.632 |
| SC2 | 0 | 8 | 10.843 |
| SC3 | -18 | 7 | 9.089 |
| SC4 | -25 | 6 | 7.347 |
| SC5 | -34 | 6 | 7.050 |
| A | 1237 mm |
|---|---|
| B | 640 mm |
| C | 685 mm |
| F | 445 mm |
| E | 885 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1237 mm |
|---|---|
| Width | 640 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.