EA-630BE8-C01 C
12.92 kW
Defrost: None
Product code: EA-150AG6-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,706 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 49.7 m² |
| Inner volume | 14.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 83 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 710 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 78.6 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-150AG6-C09 C | None |
|---|---|
| EA-150AG6-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.52 | 5.49 | 5.49 | 5.49 | 5.46 | 5.40 | 5.32 | 5.43 | 5.77 | 6.25 | 6.10 | 6.05 | 5.99 | 5.87 |
| 5 | 7.05 | 7.11 | 7.18 | 7.24 | 7.23 | 7.17 | 7.07 | 7.16 | 7.59 | 8.20 | 7.95 | 7.87 | 7.75 | 7.58 |
| 6 | 8.57 | 8.75 | 8.89 | 9.03 | 9.08 | 9.04 | 8.93 | 9.00 | 9.53 | 10.29 | 9.93 | 9.80 | 9.61 | 9.31 |
| 7 | 9.97 | 10.30 | 10.60 | 10.85 | 10.97 | 10.96 | 10.87 | 10.93 | 11.56 | 12.49 | 12.04 | 11.86 | 11.60 | 11.18 |
| 8 | 11.24 | 11.72 | 12.16 | 12.54 | 12.78 | 12.88 | 12.83 | 12.90 | 13.63 | 14.72 | 14.22 | 14.00 | 13.68 | 13.15 |
| 9 | 12.36 | 13.01 | 13.61 | 14.06 | 14.37 | 14.55 | 14.58 | 14.72 | 15.61 | 16.89 | 16.41 | 16.20 | 15.82 | 15.19 |
| 10 | 13.41 | 14.24 | 14.92 | 15.57 | 16.00 | 16.24 | 16.32 | 16.49 | 17.48 | 18.91 | 18.40 | 18.15 | 17.78 | 17.14 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.395 |
| SC2 | 0 | 8 | 12.903 |
| SC3 | -18 | 7 | 10.913 |
| SC4 | -25 | 6 | 8.887 |
| SC5 | -34 | 6 | 8.623 |
| A | 1237 mm |
|---|---|
| B | 740 mm |
| C | 685 mm |
| F | 545 mm |
| E | 885 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1237 mm |
|---|---|
| Width | 690 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.