EA-163EC7-C06 C
9.82 kW
Defrost: Electric
Product code: EA-235AG4-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,483 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 60.9 m² |
| Inner volume | 12.9 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 75 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 73.2 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-235AG4-C01 C | None |
|---|---|
| EA-235AG4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.38 | 4.43 | 4.48 | 4.53 | 4.54 | 4.51 | 4.44 | 4.58 | 4.88 | 5.30 | 5.18 | 5.14 | 5.09 | 5.02 |
| 5 | 5.45 | 5.57 | 5.69 | 5.79 | 5.82 | 5.80 | 5.72 | 5.82 | 6.18 | 6.71 | 6.48 | 6.40 | 6.28 | 6.10 |
| 6 | 6.50 | 6.71 | 6.88 | 7.05 | 7.13 | 7.12 | 7.04 | 7.12 | 7.54 | 8.16 | 7.86 | 7.74 | 7.55 | 7.25 |
| 7 | 7.45 | 7.78 | 8.08 | 8.33 | 8.46 | 8.47 | 8.39 | 8.46 | 8.95 | 9.66 | 9.30 | 9.14 | 8.90 | 8.51 |
| 8 | 8.31 | 8.76 | 9.16 | 9.51 | 9.72 | 9.79 | 9.75 | 9.81 | 10.36 | 11.17 | 10.77 | 10.57 | 10.29 | 9.80 |
| 9 | 9.09 | 9.67 | 10.19 | 10.58 | 10.87 | 10.99 | 10.99 | 11.09 | 11.74 | 12.67 | 12.25 | 12.04 | 11.70 | 11.12 |
| 10 | 9.79 | 10.51 | 11.10 | 11.66 | 12.03 | 12.21 | 12.24 | 12.35 | 13.07 | 14.10 | 13.65 | 13.42 | 13.07 | 12.45 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.648 |
| SC2 | 0 | 8 | 9.806 |
| SC3 | -18 | 7 | 8.393 |
| SC4 | -25 | 6 | 6.884 |
| SC5 | -34 | 6 | 6.555 |
| A | 1357 mm |
|---|---|
| B | 673 mm |
| C | 525 mm |
| F | 495 mm |
| E1 | 517.5 mm |
| E | 1035 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1357 mm |
|---|---|
| Width | 623 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.