EA-530AC10-C01 C
8.67 kW
Defrost: Electric
Product code: EA-240AC7-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,463 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 24.5 m² |
| Inner volume | 8.5 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 58 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| EA-240AC7-C01 C | None |
|---|---|
| EA-240AC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.47 | 3.51 | 3.54 | 3.56 | 3.55 | 3.52 | 3.47 | 3.50 | 3.70 | 3.98 | 3.86 | 3.81 | 3.74 | 3.64 |
| 5 | 4.47 | 4.60 | 4.71 | 4.79 | 4.83 | 4.82 | 4.78 | 4.81 | 5.10 | 5.50 | 5.33 | 5.27 | 5.19 | 5.06 |
| 6 | 5.37 | 5.60 | 5.82 | 6.01 | 6.14 | 6.19 | 6.17 | 6.22 | 6.59 | 7.11 | 6.90 | 6.82 | 6.71 | 6.52 |
| 7 | 6.11 | 6.46 | 6.78 | 7.02 | 7.21 | 7.33 | 7.39 | 7.49 | 7.96 | 8.65 | 8.47 | 8.39 | 8.28 | 8.09 |
| 8 | 6.80 | 7.20 | 7.64 | 8.02 | 8.29 | 8.47 | 8.57 | 8.70 | 9.25 | 10.06 | 9.85 | 9.76 | 9.63 | 9.40 |
| 9 | 7.42 | 7.96 | 8.51 | 8.99 | 9.35 | 9.59 | 9.75 | 9.91 | 10.54 | 11.47 | 11.25 | 11.15 | 11.00 | 10.72 |
| 10 | ≈ 7.93 | 8.65 | 9.32 | 9.93 | 10.38 | 10.70 | 10.91 | 11.12 | 11.83 | 12.89 | 12.66 | 12.55 | 12.38 | 12.06 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.658 |
| SC2 | 0 | 8 | 8.696 |
| SC3 | -18 | 7 | 7.104 |
| SC4 | -25 | 6 | 5.821 |
| SC5 | -34 | 6 | 5.424 |
| A | 1467 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E | 1135 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 1467 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.