EA-150AG6-C09 C
12.90 kW
Defrost: Electric
Product code: EA-240AG4-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,620 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 78.1 m² |
| Inner volume | 16.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 93 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-240AG4-C01 C | None |
|---|---|
| EA-240AG4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.60 | 5.71 | 5.81 | 5.90 | 5.93 | 5.91 | 5.85 | 6.01 | 6.40 | 6.95 | 6.78 | 6.73 | 6.66 | 6.57 |
| 5 | 6.91 | 7.14 | 7.36 | 7.53 | 7.61 | 7.61 | 7.54 | 7.67 | 8.14 | 8.83 | 8.55 | 8.44 | 8.29 | 8.05 |
| 6 | 8.19 | 8.57 | 8.90 | 9.18 | 9.31 | 9.35 | 9.29 | 9.40 | 9.96 | 10.78 | 10.41 | 10.26 | 10.03 | not rated |
| 7 | 9.33 | 9.86 | 10.33 | 10.74 | 10.99 | 11.11 | 11.06 | 11.15 | 11.80 | 12.77 | 12.33 | 12.14 | 11.86 | not rated |
| 8 | 10.32 | 11.02 | 11.65 | 12.11 | 12.47 | 12.65 | 12.68 | 12.84 | 13.61 | 14.72 | 14.28 | 14.07 | not rated | not rated |
| 9 | 11.22 | 12.10 | 12.81 | 13.50 | 13.97 | 14.22 | 14.30 | 14.47 | 15.34 | 16.59 | 16.10 | 15.86 | not rated | not rated |
| 10 | ≈ 12.04 | 12.94 | 13.98 | 14.83 | 15.41 | 15.77 | 15.90 | 16.11 | 17.07 | 18.46 | 17.94 | 17.67 | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 17.937 |
| SC2 | 0 | 8 | 12.836 |
| SC3 | -18 | 7 | 10.859 |
| SC4 | -25 | 6 | 8.901 |
| SC5 | -34 | 6 | 8.283 |
| A | 1467 mm |
|---|---|
| B | 686 mm |
| C | 605 mm |
| F | 495 mm |
| E1 | 568 mm |
| E | 1135 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 1467 mm |
|---|---|
| Width | 686 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.