EA-630BE8-C01 C
12.92 kW
Defrost: None
Product code: EA-245AC7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 10,673 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 33.4 m² |
| Inner volume | 11.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 77 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-245AC7-C01 C | None |
|---|---|
| EA-245AC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.17 | 5.17 | 5.18 | 5.17 | 5.12 | 5.04 | 4.94 | 4.97 | 5.24 | 5.62 | 5.43 | 5.36 | 5.26 | 5.10 |
| 5 | 6.75 | 6.88 | 7.00 | 7.06 | 7.07 | 7.02 | 6.92 | 6.96 | 7.36 | 7.93 | 7.67 | 7.57 | 7.44 | 7.24 |
| 6 | 8.17 | 8.47 | 8.74 | 8.98 | 9.12 | 9.14 | 9.06 | 9.12 | 9.66 | 10.41 | 10.07 | 9.94 | 9.74 | 9.46 |
| 7 | 9.36 | 9.82 | 10.23 | 10.54 | 10.77 | 10.91 | 10.97 | 11.10 | 11.79 | 12.80 | 12.50 | 12.38 | 12.21 | 11.90 |
| 8 | 10.46 | 11.03 | 11.60 | 12.10 | 12.44 | 12.65 | 12.76 | 12.93 | 13.74 | 14.92 | 14.59 | 14.45 | 14.24 | 13.90 |
| 9 | 11.35 | 12.21 | 12.95 | 13.61 | 14.08 | 14.39 | 14.57 | 14.78 | 15.71 | 17.08 | 16.71 | 16.55 | 16.31 | 15.91 |
| 10 | 12.31 | 13.31 | 14.25 | 15.08 | 15.69 | 16.11 | 16.36 | 16.63 | 17.69 | 19.24 | 18.85 | 18.68 | 18.42 | 17.96 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.854 |
| SC2 | 0 | 8 | 12.931 |
| SC3 | -18 | 7 | 10.646 |
| SC4 | -25 | 6 | 8.739 |
| SC5 | -34 | 6 | 8.247 |
| A | 1767 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1767 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.