EA-340AG6-C01 C
18.66 kW
Defrost: None
Product code: EA-245AE4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 8,698 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 79.9 m² |
| Inner volume | 17.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 97 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø35 |
| EA-245AE4-C01 C | None |
|---|---|
| EA-245AE4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.87 | 7.93 | 7.98 | 8.03 | 8.01 | 7.94 | 7.83 | 8.01 | 8.53 | 9.24 | 9.03 | 8.96 | 8.88 | 8.69 |
| 5 | 10.05 | 10.28 | 10.45 | 10.61 | 10.66 | 10.60 | 10.47 | 10.62 | 11.27 | 12.19 | 11.82 | 11.70 | 11.53 | 11.29 |
| 6 | 12.06 | 12.50 | 12.91 | 13.26 | 13.43 | 13.43 | 13.28 | 13.42 | 14.22 | 15.37 | 14.85 | 14.66 | 14.37 | 13.90 |
| 7 | 13.75 | 14.42 | 15.02 | 15.46 | 15.78 | 15.94 | 15.94 | 16.14 | 17.13 | 18.58 | 18.04 | 17.78 | 17.38 | 16.73 |
| 8 | 15.31 | 16.23 | 16.96 | 17.66 | 18.12 | 18.37 | 18.42 | 18.64 | 19.78 | 21.44 | 20.80 | 20.53 | 20.11 | 19.41 |
| 9 | 16.73 | 17.81 | 18.88 | 19.81 | 20.43 | 20.78 | 20.90 | 21.17 | 22.46 | 24.32 | 23.61 | 23.28 | 22.78 | 21.93 |
| 10 | 17.93 | 19.38 | 20.71 | 21.88 | 22.68 | 23.18 | 23.39 | 23.71 | 25.15 | 27.23 | 26.46 | 26.08 | 25.51 | 24.49 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 26.461 |
| SC2 | 0 | 8 | 18.643 |
| SC3 | -18 | 7 | 15.613 |
| SC4 | -25 | 6 | 12.911 |
| SC5 | -34 | 6 | 12.167 |
| A | 1767 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø35 |
| Length | 1767 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.