EA-245AE4-C01 C
18.64 kW
Defrost: None
Product code: EA-340AG6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,500 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 84.4 m² |
| Inner volume | 24.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 123 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø42 |
| EA-340AG6-C01 C | None |
|---|---|
| EA-340AG6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.46 | 8.36 | 8.32 | 8.32 | 8.27 | 8.18 | 8.06 | 8.26 | 8.80 | 9.54 | 9.33 | 9.26 | 9.18 | 9.07 |
| 5 | 10.79 | 10.76 | 10.79 | 10.83 | 10.79 | 10.69 | 10.53 | 10.68 | 11.34 | 12.27 | 11.89 | 11.76 | 11.58 | 11.31 |
| 6 | 13.07 | 13.16 | 13.29 | 13.42 | 13.42 | 13.33 | 13.14 | 13.25 | 14.02 | 15.15 | 14.62 | 14.41 | 14.12 | 13.65 |
| 7 | 15.33 | 15.58 | 15.79 | 16.03 | 16.10 | 16.04 | 15.84 | 15.92 | 16.83 | 18.17 | 17.49 | 17.22 | 16.81 | 16.15 |
| 8 | 17.44 | 17.88 | 18.29 | 18.66 | 18.82 | 18.77 | 18.59 | 18.66 | 19.72 | 21.25 | 20.49 | 20.15 | 19.65 | 18.81 |
| 9 | 19.39 | 20.03 | 20.65 | 21.19 | 21.49 | 21.54 | 21.38 | 21.45 | 22.67 | 24.42 | 23.56 | 23.16 | 22.56 | 21.56 |
| 10 | 21.16 | 22.03 | 22.84 | 23.55 | 23.95 | 24.08 | 24.04 | 24.21 | 25.62 | 27.59 | 26.64 | 26.20 | 25.52 | 24.36 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 26.643 |
| SC2 | 0 | 8 | 18.661 |
| SC3 | -18 | 7 | 16.075 |
| SC4 | -25 | 6 | 13.290 |
| SC5 | -34 | 6 | 13.103 |
| A | 2017 mm |
|---|---|
| B | 686 mm |
| C | 605 mm |
| F | 495 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 1685 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø42 |
| Length | 2017 mm |
|---|---|
| Width | 686 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.